Mich. Admin. Code R. 408.31063 - [Rescinded effective 8/29/2025] Insulation and fenestration criteria
Rule 1063. Insulation and fenestration criteria. Table R402.1.1 of the code is amended to read as follows:
TABLE R 402.1.1 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa
|
CLIMATE ZONE |
FENESTRATION U-FACTOR |
SKYLIGHTb U-FACTOR |
CEILING R-Value |
WOOD FRAME WALL R-VALUE |
MASS WALL R-VALUEg |
FLOOR R-VALUE |
BASEMENTc WALL R-VALUE |
SLAB d R-VALUE AND DEPTH |
CRAWL SPACEc WALL R-VALUE |
|
5A |
0.32 |
0.55 |
38 |
20 or 13 + 5f |
13/17 |
30e |
10/13 |
10, 2ft |
15/19 |
|
6A |
0.32 |
0.55 |
49 |
20 or 13 + 5f |
15/20 |
30e |
15/19 |
10, 4ft |
15/19 |
|
7 |
0.32 |
0.55 |
49 |
20 or 13 + 5f |
19/21 |
38e |
15/19 |
10, 4ft |
15/19 |
a. R-values are minimums. U-factors are maximums. When insulation is installed in a cavity that is less than the label or design thickness of the insulation, the installed R-value of the insulation shall not be less than the R-values specified in the table.
b. The fenestration U-factor column excludes skylights.
c. "15/19" means R-15 continuous insulation on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall. "15/19" may be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the home. "10/13" means R-10 continuous insulation on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.
d. R-5 shall be added to the required slab edge R-values for heated slabs.
e. Or insulation sufficient to fill the framing cavity, R-19 minimum.
f. First value is cavity insulation, second is continuous insulation or insulated siding, so "13 + 5" means R-13 cavity insulation plus R-5 continuous insulation or insulated siding. If structural sheathing covers 40 % or less of the exterior, continuous insulation R-value may be reduced by no more than R-3 in the locations where structural sheathing is used to maintain a consistent total sheathing thickness.
g. The second R-value applies when more than half the insulation is on the interior of the mass wall.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Rule 1063. Insulation and fenestration criteria. Table R402.1.1 of the
TABLE R 402.1.1 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa
| CLIMATE ZONE | FENESTRATION U-FACTOR | SKYLIGHTb U-FACTOR | CEILING R-Value | WOOD FRAME WALL R-VALUE | MASS WALL R-VALUEg | FLOOR R-VALUE | WALL R-VALUE | SLAB d R-VALUE AND DEPTH | CRAWL SPACEc WALL R-VALUE |
| 5A | 0.32 | 0.55 | 38 | 20 or 13 + 5f | 13/17 | 30e | 10/13 | 10, 2ft | 15/19 |
| 6A | 0.32 | 0.55 | 49 | 20 or 13 + 5f | 15/20 | 30e | 15/19 | 10, 4ft | 15/19 |
| 7 | 0.32 | 0.55 | 49 | 20 or 13 + 5f | 19/21 | 38e | 15/19 | 10, 4ft | 15/19 |
a. R-values are minimums. U-factors are maximums. When insulation is installed in a cavity that is less than the
b. The fenestration U-factor column excludes skylights.
c. "15/19" means R-15 continuous insulation on the interior or exterior of the
d. R-5 shall be added to the required slab edge R-values for heated slabs.
e. Or insulation sufficient to fill the framing cavity, R-19 minimum.
f. First value is cavity insulation,
g. The