Mich. Admin. Code R. 408.40206 - Restricted zone requirements
Rule 206.
(1)
For walls greater than 8 feet in height, a restricted zone shall be established
prior to the start of the construction of the wall. The restricted zone shall
meet all of the following requirements (see figure 1):
(a) Be equal to the height of the constructed
wall plus a minimum of 4 feet and run the entire length of the wall plus a
minimum of 4 feet beyond the ends of the wall.
(b) Be established on both sides and ends of
the wall.
(c) Be limited to entry
by employees trained in accordance with
R
408.40205.
(d) Remain in place until the wall has
obtained its final lateral support.
(e) Be delineated by signing in accordance
with
R
408.40207.
(2) When a restricted zone extends onto or
across roadways or other adjacent areas, protection shall be provided as
prescribed in construction safety standard part 22 signals, signs, tags, and
barricades,
R
408.42223 traffic control, or by other
methods.
(3) If restricted zones
cannot be installed or maintained as prescribed by these rules, alternative
protective methods shall be provided.
Drawings/plans or calculations shall be prepared by a qualified person and available at the jobsite.
(4) For multi-story structures the restricted
zone shall be determined by a qualified person.