Mich. Admin. Code R. 408.40211 - Wall bracing design
Rule 211.
(1) A
wall bracing system shall be designed by a qualified person and capable of
providing stability to the wall for a wind speed of 40 miles per
hour.
(2) A wall bracing system
shall be installed in accordance with 1 of the following:
(a) A triangle wall bracing system as
prescribed in
R
408.40212.
(b) A bracing plan that is designed using
acceptable engineering practices and the engineering content of the mason
contractors association of America, standard practice for bracing masonry walls
under construction, chapters 5 and 6 and their commentaries, July 2001 Edition,
adopted by reference in
R
408.40202. Wall bracing erection drawings/plans or
calculations and specifications shall be available at the jobsite. Bracing
schemes for walls matching examples specifically outlined in the mason
contractors association of America, masonry wallbracing design handbook, March
2003 Edition, adopted by reference in
R
408.40202, satisfy these requirements.