Mich. Admin. Code R. 408.41877 - Storage of LPG containers
Rule 1877.
(1)
This rule applies to the storage of portable containers whether filled or empty
if they have been in service.
(2)
Storage of L.P. gas within buildings is prohibited.
(3) Storage outside of buildings, for
containers awaiting use, shall be located away from the nearest building or
group of buildings as specified in table 4.
(4) Table 4 reads as follows:
TABLE 4
| QUANTITY OF L.P. GAS STORED | DISTANCE (FEET) FROM A BUILDING |
| 500 lbs. or less | 0 |
| 501 to 6,000 lbs. | 10 |
| 6,001 to 10,000 lbs. | 20 |
| over 10,000 lbs. | 25 |
(5) Containers shall be stored within a
suitable ventilated enclosure or otherwise protected against tampering, and
located as specified in table 4.
(6) When L.P. gas and 1 or more other gases
are stored or used in the same area, the containers shall be marked to identify
their content. Marking shall be in compliance with The Compressed Gas
Association Standard CGA C7 "Guide To The Preparation Of Precautionary Labeling
And Marking Of Compressed Gas Containers," 2000 edition, which is adopted by
reference in
R
408.41802.