Mich. Admin. Code R. 460.2382 - Heating value; authorized variations
Rule 82.
(1) The
heating value of substitute natural gas and mixed gas must be considered as
being under the control of the utility. The average heating value on 1 day must
not be more than or less than the standard total heating value range set forth
in the utility's rules. A utility shall not add air to a gas stream if this
results in a heating value that is below 1,000 British thermal units per
standard cubic foot.
(2) The average
monthly heating value of gas that is supplied by a utility shall be 1,025
British thermal units per standard cubic foot, plus or minus 75 British thermal
units. A greater variation may be approved by the commission upon a showing by
the utility that the variation will not adversely affect the efficient and
satisfactory operation of its customers gas utilization
equipment.