Minn. R. agency 151, ch. 1305, pt. 1305.0403 - SECTION 403, HIGH-RISE BUILDINGS
Subpart
1.
IBC section 403.2.1.2.
IBC section 403.2.1.2 is deleted in its entirety.
Subp. 2. [Repealed, ]
Subp. 3.
IBC section 403.4.8.3.
IBC section 403.4.8.3 is amended to read as follows:
403.4.8.3
Standby power loads.
The following are classified as standby power loads:
1. power and lighting for the fire command
center required by Section 403.4.6;
2. ventilation and automatic fire detection
equipment for smokeproof enclosures; and
3. passenger elevators serving occupied
floors more than 75 feet (22, 860 mm) above the lowest level of fire department
vehicle access.