Minn. R. agency 151, ch. 1305, pt. 1305.0414 - SECTION 414, HAZARDOUS MATERIALS
Subpart
1.
Section 414.2.4.
IBC Section 414.2.4 is amended to read as follows:
414.2.4
Fire-resistance-rating
requirements. The required fire-resistance rating for fire barrier
assemblies shall be in accordance with Table 414.2.2.
Subp. 2.
Section 414.2.6.
IBC Section 414.2 is amended by adding a subsection to read as follows:
414.2.6
Hazardous
materials above the third floor in laboratories in Group B, E, and I-2
occupancies. Control areas containing laboratories located above the
third floor in Group B, E, or I-2 occupancies may be exempt from the provisions
in Sections 414.2.1 through 414.2.4 if all of the following conditions are met:
1. Buildings containing the laboratories are
equipped throughout with automatic sprinkler protection installed in accordance
with Section 903.3.1.1;
2. Control
areas containing laboratories located above the third floor are separated from
each other and other portions of the building by a fire barrier having a
fire-resistance rating of not less than two hours;
3. The maximum amount of hazardous materials
in storage and in use in control areas containing laboratories does not exceed
ten percent of the maximum allowable quantities listed in Tables 307.1(1) and
307.1(2) with all increases allowed in the footnotes of those tables;
and
4. The maximum number of
control areas containing laboratories shall not exceed 5 per floor.