Minn. R. agency 151, ch. 1305, pt. 1305.1024 - SECTION 1024, EXIT PASSAGEWAYS
IBC section 1024.6 is amended to read as follows:
1024.6 Penetrations. Penetrations into or
through an interior exit passageway are prohibited except for the following:
1. Equipment and ductwork necessary for
independent ventilation or pressurization.
2. Fire protection systems.
3. Security systems that serve the exit
passageway.
4. Wiring that serves
the exit passageway.
5. Two-way
communication systems that serve the exit passageway.
6. Electrical raceway for fire department
communication systems.
7.
Electrical raceway serving the exit passageway and terminating in a steel box
not exceeding 16 square inches (0.010 m2).
Such penetrations shall be protected in accordance with Section 714. There shall not be penetrations or openings, whether protected or not, between adjacent interior exit stairways and ramps or adjacent exit passageways.
(The exception to Section 1024.6 is deleted.)
IBC section 1023.6 is amended to read as follows:
1023.6
Penetrations. Penetrations into and openings through an exit
passageway are prohibited except for required exit doors, equipment, and
ductwork necessary for independent pressurization, sprinkler piping,
standpipes, electrical raceway for fire department communication, and
electrical raceway serving the exit passageway and terminating at a steel box
not exceeding 16 square inches (0.010 m2). Such
penetrations shall be protected in accordance with section 714. There shall be
no penetrations or communicating openings, whether protected or not, between
any other exit passageway.