Minn. R. agency 151, ch. 1305, pt. 1305.3003 - SECTION 3003, EMERGENCY OPERATIONS
Subpart 1.
IBC section 3003.1.1.
IBC section 3003.1.1 is modified to read:
3003.1.1
Manual transfer. At
elevator locations where standby power is required, standby power shall be
manually transferable to all elevators in each bank. Standby power shall not be
transferred from elevator banks where standby power is required to elevator
banks where standby power is not required.
Subp. 2.
IBC section 3003.1.3.
IBC section 3003.1.3 is modified to read:
3003.1.3 Two or more elevators. Where two or
more elevators are controlled by a common operating system, where standby power
is required, all elevators controlled by that common operating system shall
automatically transfer to standby power within 60 seconds after failure of
normal power where the standby power source is of sufficient capacity to
operate all elevators at the same time. Where the standby power source is not
of sufficient capacity to operate all elevators at the same time, the elevators
shall operate according to ASME A17.1/CSA B44-2016 2.27.2.