Minn. R. agency 151, ch. 1309, pt. 1309.0702 - SECTION R702, INTERIOR COVERING
Subpart 1.
IRC
Table R702.1(3).
Table R702.1(3) is amended to read as follows:
TABLE R702.1(3) CEMENT PLASTER PROPORTIONS, PARTS BY VOLUME
| COAT | CEMENT PLASTER TYPE | CEMENTITIOUS MATERIALS | VOLUME OF AGGREGAT PER SUM OF SEPARATE VOLUMES OF CEMENTITIOUS MATERIALSb | |||
| Portland Cement Type I, II or III or Blended Cement Type IP, I(PM), IS or I(SM) | Plastic Cement | Masonry Cement Type M, S or N | Lime | |||
| First | Portland or blended | 1 | 3/4 - 1-1/2a | 2-1/2 - 4 | ||
| Masonry | 1 | 2-1/2 - 4 | ||||
| Plastic | 1 | 2-1/2 - 4 | ||||
| Second | Portland or blended | 1 | 3/4 - 1-1/2 | 3-5 | ||
| Masonry | 1 | 3-5 | ||||
| Plastic | 1 | 3-5 | ||||
| Finish | Portland or blended | 1 | 3/4-2 | 1-1/2 - 3 | ||
| Masonry | 1 | 1-1/2 - 3 | ||||
| Plastic | 1 | 1-1/2 - 3 | ||||
For SI: 1 inch = 25.4 mm, 1 pound = 0.545 kg.
a. Lime by volume of 0 to 3/4 shall be used
when the plaster will be placed over low-absorption surfaces such as dense clay
tile or brick.
b. The same or
greater sand proportion shall be used in the second coat than used in the first
coat.
Subp. 2.
IRC
section R702.7 Vapor retarders.
Section R702.7 is amended to read as follows:
R702.7
Vapor retarders. A Class
I or II vapor retarder is required on the interior side of frame walls in
Climate Zones 6 and 7. Class II vapor retarders are permitted only when
specified on the construction documents.