Minn. R. agency 151, ch. 1323, pt. 1323.0543 - SECTION 5.4.3, AIR LEAKAGE
Subpart 1.
ASHRAE 90.1 section 5.4.3.1 Continuous air barrier.
ASHRAE 90.1 section 5.4.3.1 is amended by deleting exception 1.
Subp. 2.
ASHRAE
90.1 section 5.4.3.1.1 Whole-building air leakage.
ASHRAE 90.1 section 5.4.3.1.1 is amended by adding exception 4 to read as follows:
4. For buildings
or portions of buildings enclosing Group R or Group I occupancies, the measured
air leakage shall not exceed 0.30 cfm/ft2 (1.5 L/s
m2) of the testing unit enclosure area at a pressure
differential of 0.2 inch water gauge (50 Pa). Where multiple dwelling units or
sleeping units or other occupiable conditioned spaces are contained within one
building thermal envelope, each unit shall be considered an individual testing
unit, and the building air leakage shall be the weighted average of all testing
unit results, weighted by each testing units enclosure area. Units shall be
tested separately with an unguarded blower door test as follows:
a. Where buildings have fewer than eight
testing units, each testing unit shall be tested.
b. For buildings with eight or more testing
units, the greater of seven units or 20 percent of the testing units in the
building shall be tested, including a top floor unit, a ground floor unit, and
a unit with the largest testing unit enclosure area. For each tested unit that
exceeds the maximum air leakage rate, an additional two units shall be tested,
including a mixture of testing unit types and locations.