Minn. R. agency 151, ch. 1323, pt. 1323.0643 - SECTION 6.4.3, CONTROLS AND DIAGNOSTICS
Subpart 1.
ASHRAE 90.1 section
6.4.3.4.2 Ventilation system control.
ASHRAE 90.1 section 6.4.3.4.2 is amended by modifying the exception 1 to read as follows:
1.
[Reserved].
Subp. 2.
ASHRAE 90.1 section 6.4.3.4.2 Ventilation system control.
ASHRAE 90.1 section 6.4.3.4.2 is amended by modifying the exception 2 to read as follows:
2.
Nonmotorized dampers are acceptable in systems with a design outdoor air
intake, relief, or exhaust capacity of 300 cfm or less. Nonmotorized dampers
for outdoor air intakes must be protected from direct exposure to
wind.