Minn. R. agency 151, ch. 1323, pt. 1323.0643 - SECTION 6.4.3, CONTROLS AND DIAGNOSTICS

Subpart 1. ASHRAE 90.1 section 6.4.3.4.2 Ventilation system control.

ASHRAE 90.1 section 6.4.3.4.2 is amended by modifying the exception 1 to read as follows:

1. [Reserved].
Subp. 2. ASHRAE 90.1 section 6.4.3.4.2 Ventilation system control.

ASHRAE 90.1 section 6.4.3.4.2 is amended by modifying the exception 2 to read as follows:

2. Nonmotorized dampers are acceptable in systems with a design outdoor air intake, relief, or exhaust capacity of 300 cfm or less. Nonmotorized dampers for outdoor air intakes must be protected from direct exposure to wind.

Notes

Minn. R. agency 151, ch. 1323, pt. 1323.0643
39 SR 1605 47 SR 983