Minn. R. 1341.0404 - A117.1 SECTION 404, DOORS AND DOORWAYS
Subpart
1.
A117.1 Section 404.3.2, Maneuvering clearances.
A117.1 Section 404.3.2 is amended to read as follows:
404.3.2
Maneuvering Clearances.
Maneuvering clearances at power-assisted doors shall comply with Section
404.2.3. Clearances at automatic doors and gates without standby power and
serving an accessible means of egress shall comply with Section 404.2.3.
Exception: Automatic doors and gates which remain open in the power-off condition.
Subp. 2.
A117.1 Section 404.3.5,
Control switches.
A117.1 Section 404.3.5 is amended to read as follows:
404.3.5
Control Switches.
Manually operated control switches shall comply with Section 404.3.5.
404.3.5.1
Interior Location.
Manually operated control switches at interior locations shall comply with
Section 309. The clear floor space adjacent to the control switch shall be
located beyond the arc of the door swing.
404.3.5.2
Exterior Location.
Manually operated control switches at exterior locations shall comply with
Sections 309.2 and 309.4. The clear floor space adjacent to the control switch
shall be located beyond the arc of the door swing, be centered on the control
switch, and be positioned for a parallel approach to the control switch.
Control switches shall have a three-inch (75 mm) minimum dimension measured at
at least one point, such as diagonal, diameter, or one side. Control switches
shall be mounted 30 inches (760 mm) minimum, measured to the bottom of the
control switch, and 36 inches (915 mm) maximum, measured to the top of the
control switch, above the finished floor.