Minn. R. 1346.0301 - SECTION 301 GENERAL
IMC Section 301.4 is amended to read as follows:
301.4
Listed and labeled.
Appliances regulated by this code shall be listed and labeled to an appropriate
standard by a nationally recognized testing laboratory which is qualified to
evaluate the appliance, unless otherwise approved in accordance with the
administrative provisions of the Minnesota State Building Code, Minnesota
Rules, chapter 1300. The approval of unlisted appliances shall be based upon
engineering evaluation. Unlisted appliances shall be installed with clearances
to combustibles in accordance with NFPA 211-2006 Standard for Chimneys,
Fireplaces, Vents, and Solid Fuel Burning Appliances; NFPA 31-2006 Standard for
the Installation of Oil Burning Equipment; or NFPA 90B-2009 Standard for the
Installation of Warm Air Heating and Air-Conditioning Systems, as applicable to
the unlisted appliances. Unlisted appliances with a fuel input rating of less
than 12,500,000 Btu/hr (3,660 kW) shall have fuel trains, controls, and safety
devices installed in accordance with Part CF, Combustion Side Control, of ASME
CSD-1-2006. Unlisted appliances with a fuel input rating of 12,500,000 Btu/hr
(3,660 kW) or greater shall have fuel trains, controls, and safety devices
installed in accordance with NFPA 85-2007.