Minn. R. agency 151, ch. 1346, MINNESOTA MECHANICAL CODE, pt. 1346.0309 - SECTION 309 TEMPERATURE CONTROL
IMC Section 309 is amended by adding a section to read as follows:
309.2
Balancing. All mechanical ventilation and hydronic systems shall be
capable of being balanced in accordance with this section.
309.2.1
Mechanical ventilation system
balancing. Mechanical ventilation systems shall provide airflow rates
within +/-10 percent of design capacities and fan speed shall be adjusted to
meet design airflow conditions.
Exceptions:
1. Speed adjustment is not required for fan
motors rated at one horsepower (0.746 kW) or less.
2. Residential exhaust-only ventilation
systems shall be capable of exhausting the minimum ventilation rate required in
the Minnesota Energy Code, Minnesota Rules, chapter 7670 or 7672.
309.2.2
Hydronic system
balancing. Hydronic systems shall provide flow rates within +/-10
percent of design capacities and pump impellers shall be trimmed or pump speed
shall be adjusted to meet design flow conditions.
Exception: Impeller trimming or speed adjustment is not required for pump motors rated at five horsepower (3.73 kW) or less.
309.2.3
Systems balancing reports. Systems balancing reports shall verify system
performance and shall specify that the minimum amount of outdoor air required
in amended Chapter 4 is provided to the ventilation system. Systems balancing
reports shall be submitted to the building official upon request.