Minn. R. 1346.0506 - SECTION 506 COMMERCIAL KITCHEN HOOD VENTILATION SYSTEM DUCTS AND EXHAUST EQUIPMENT
Subpart
1.
Section 506.3.
IMC section 506.3 and all subsections are deleted in their entirety and replaced with the following:
506.3
Ducts serving Type I
hoods. Commercial kitchen exhaust systems serving Type I hoods shall be
designed, constructed and installed in accordance with NFPA 96, Standard for
Ventilation Control and Fire Protection of Commercial Cooking Operations and
ASHRAE 154 Ventilation for Commercial Cooking Operations.
Subp. 2.
Section 506.4.
IMC section 506.4 is amended and a subsection added to read as follows:
506.4
Ducts serving
Type II hoods. Commercial kitchen exhaust systems serving Type II hoods
shall comply with sections 506.4.1 and 506.4.2 and ASHRAE 154.
506.4.1
Ducts. Ducts and plenums
serving Type II hoods shall be constructed of rigid metallic materials. Duct
construction, installation, bracing, and supports shall comply with chapter 6.
Ducts subject to positive pressure or conveying moisture-laden air, or both,
and ducts conveying waste-heat-laden air shall be tested pursuant to section
.1.1.
506.4.1.1
Testing. Ducts
shall be tested in accordance with ASHRAE 154 requirements for duct leakage
testing.
506.4.2
Type II terminations. Exhaust outlets serving Type II hoods shall
terminate in accordance with the hood manufacturers installation instructions
and shall comply with all of the following:
1. Exhaust outlets shall terminate not less
than three feet (914 mm) in any direction from openings into the
building.
2. Outlets shall
terminate not less than ten feet (3,048 mm) from property lines or buildings on
the same lot.
3. Outlets shall
terminate not less than ten feet (3,048 mm) above grade.
4. Outlets that terminate above a roof shall
terminate not less than 30 inches (762 mm) above the roof surface.
5. Outlets shall terminate not less than 30
inches (762 mm) from exterior vertical walls.
6. Outlets shall be protected against local
weather conditions.
7. Outlets
shall not be directed onto walkways.
8. Outlets shall meet the provisions for
exterior wall opening protectives in accordance with the International Building
Code.
Subp.
2a.
Section 506.5.
IMC section 506.5 and all subsections are deleted in their entirety. Exhaust equipment shall comply with NFPA 96 and ASHRAE 154.
Subp. 2b. [Repealed, 44 SR
1085]
Subp. 3. [Repealed, 44 SR
1085]
Subp. 4. [Repealed, 44 SR
1085]