Minn. R. 1346.0901 - SECTION 901 GENERAL
IMC Section 901 is amended by adding a section to read as follows:
Exception: Unvented infrared heaters may be installed when mechanical ventilation is provided to exhaust at least 4 cubic feet per minute (cfm) (0.0203 m3/s) per 1000 Btu/hr (0.292 kW) input and it is electrically interlocked with the heater. Makeup air shall be provided to the space to be heated.