Minn. R. agency 144, ch. 4658, ELECTRICAL SYSTEMS; NEW CONSTRUCTION, pt. 4658.4625 - BEDROOM RECEPTACLES; NEW CONSTRUCTION

Each resident bedroom must have a minimum of two duplex receptacles mounted on the wall at the head of the bed, and one receptacle mounted on each side of the bed, for a total of four electrical outlets per bed. In addition to the receptacles at the head and side of each bed, each resident bedroom must be provided with two additional duplex receptacles, conveniently located on adjacent walls for resident use. At least one receptacle must be located between 16 inches and 20 inches above the floor, and be accessible for resident use.