Minn. R. agency 144, ch. 4675, PATIENT TREATMENT AREAS, pt. 4675.0900 - SURGICAL SUITE
The surgical suite shall include the following elements:
A. Location and arrangement
shall prevent unrelated traffic through the suite.
B. One or more operating rooms. Each
operating room shall have a floor area of not less than 225 square feet with a
minimum dimension of 15 feet. Walls, ceilings, and floors shall have smooth
cleanable surfaces. Equipment shall include an operating table, surgical light,
and provision for oxygen and vacuum. Operating rooms using flammable anesthetic
shall be designed in accordance with the National Electrical Code, 1975
edition, for such use.
C. A scrub
sink with foot, knee, or automatic controls adjacent to the entrance to each
operating room, or in a central location convenient to such rooms.
D. A clean work room for assembly and storage
of clean and sterile surgical supplies and instruments. It shall contain a work
counter, sink with institutional fittings for hand washing, and storage
cabinets or shelving. A high-speed sterilizer is required in this area if a
sterilizer is not provided in the general clean and sterile supply
room.
E. A soiled work room for
disposal or collection of soiled materials generated in surgery. It shall
contain a flushing rim sink, work counter and sink with institutional fittings,
and space for collection of waste and soiled linen. Institutional fittings
shall include: mixing faucet with gooseneck spout, wrist-action controls, and
open grid strainer.
F. Space for
cleaning, testing, and storage of anesthetic equipment. It shall contain a work
counter and sink with institutional fittings.
G. A janitors closet with a service sink and
shelving for cleaning supplies for exclusive use by the surgical
suite.
H. Gowning areas for the
surgical staff, both male and female. Each area shall contain lockers; toilet;
and a lavatory with open grid strainer, wrist- , foot- , or knee-control mixing
faucet for hand washing; and separate storage provisions for clean and soiled
gowns and boots. The areas shall be arranged to provide initial entry without
entering the operating suite and shall permit direct access to the surgical
suite by staff prepared for surgery.