Minn. R. agency 151, ch. 7511, pt. 7511.0503 - SECTION 503, FIRE APPARATUS ACCESS ROADS
IFC section 503.1.1 is amended to read as follows:
Exception: Fire apparatus access roads need not be provided where there are two or fewer Group R-3 or Group U occupancy buildings.
IFC section 503.2.1 is amended by adding an exception as follows:
Exception: Where the road serves Group R buildings that are equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.1.1, 903.1.2, or 903.1.3, the minimum unobstructed width can be reduced to 16 feet (4,877 mm).
IFC section 503.2.5 is amended by adding an exception as follows:
Exception: Where the dead-end road serves Group R buildings that are equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2, or 903.3.1.3, the maximum dead-end length distance is permitted to be increased up to 300 feet (91.4 m).