Minn. R. agency 151, ch. 7511, pt. 7511.0508 - SECTION 508, FIRE PROTECTION WATER SUPPLIES
IFC Section 508.5.1 is amended to read:
508.5.1
Where required. Where a
portion of the facility or building hereafter constructed or moved into or
within the jurisdiction is more than 300 feet (91.5 m) from a hydrant on a fire
apparatus access road, as measured by an approved route around the exterior of
the facility or building, on-site fire hydrants and mains shall be provided
where required by the fire code official.
Exceptions:
1. For Group R-3 and Group U occupancies, the
distance requirement shall be 400 feet (122 m).
2. For buildings equipped throughout with an
approved automatic sprinkler system installed in accordance with Section
903.3.1.1 or 903.3.1.2, the distance requirement shall be 400 feet (122
m).