Minn. R. agency 151, ch. 7511, pt. 7511.1024 - SECTION 1024, EXIT PASSAGEWAYS
IFC section 1024.6 is amended to read as follows:
1024.6
Penetrations.
Penetrations into or through an interior exit passageway are prohibited except
for the following:
1. Equipment and ductwork
necessary for independent ventilation or pressurization.
2. Fire protection systems.
3. Security systems that serve the exit
passageway.
4. Wiring that serves
the exit passageway.
5. Two-way
communication systems that serve the exit passageway.
6. Electrical raceway for fire department
communications systems.
7.
Electrical raceway serving the exit passageway and terminating in a steel box
not exceeding 16 square inches (0.010 m2).
Such penetrations shall be protected in accordance with Section 714 of the Building Code. There shall not be penetrations or communication openings, whether protected or not, between adjacent interior exit stairways and ramps or adjacent exit passageways.
(The exception to Section 1024.6 is deleted.)