Minn. R. agency 151, ch. 7511, pt. 7511.4600 - CHAPTER 46 - ADULT DAY CARE CENTERS, RESIDENTIAL HOSPICE FACILITIES AND SUPERVISED LIVING FACILITIES
The IFC is amended by adding Chapter 46 to read:
CHAPTER 46
ADULT DAY CARE CENTERS, RESIDENTIAL HOSPICE FACILITIES
AND SUPERVISED LIVING FACILITIES
SECTION 4601
GENERAL
4601.1
Requirements. Adult day
care centers, residential hospice facilities and supervised living facilities
shall meet the requirements of this chapter.
SECTION 4602
ADULT DAY CARE CENTERS
4602.1
Classification of adult day
care centers. Adult day care centers are classified in accordance with
the following and must meet the fire safety requirements for the designated
occupancy classification.
4602.1.1
Serving only participants capable of self-preservation. Centers serving
only participants who are capable of taking appropriate action for
self-preservation under emergency conditions shall meet all applicable
requirements for Group E occupancies.
4602.1.2
Serving only participants not
capable of self-preservation. Centers serving only participants who are
not capable of taking appropriate action for self-preservation under emergency
conditions shall meet all applicable requirements for Group I-4
occupancies.
4602.1.3
Serving both participants capable and participants not capable of
self-preservation. Centers serving a population that includes both
participants who are capable and participants who are not capable of taking
appropriate action for self-preservation under emergency conditions shall meet
the occupancy requirements for Group I-4 or Group E occupancies. In addition to
the requirements for Group E occupancies, the center shall meet the
requirements set forth in Sections 4602.1.3.1 through 4602.1.3.4.
4602.1.3.1
Population. Not more
than 50 percent of the center's licensed capacity shall be made up of
participants who are not capable of taking appropriate action for
self-preservation under emergency conditions.
4602.1.3.2
Location. The center
must be located on a floor level with all exits directly to grade without any
intervening stairs.
4602.1.3.3
Fire alarm and detection. The center shall be protected with a
complete automatic fire detection system consisting of automatic smoke
detection in all corridors and at the top of all stairways and automatic
detection in boiler and furnace rooms, kitchens, storage rooms, janitor
closets, laundries, and other hazardous areas. In buildings equipped with
manual fire alarm systems, the manual fire alarm and automatic detection
systems shall be electrically interconnected.
4602.1.3.4
Evacuation time. The
center shall demonstrate the ability to evacuate the entire population of the
center within three minutes.
SECTION 4603
RESIDENTIAL HOSPICE FACILITIES
4603.1
Classification of residential hospice facilities. Residential hospice
facilities meeting the fire-protection provisions of Chapter 22 of the National
Fire Protection Association Standard No. 101 (Quincy, Massachusetts, 1997) for
impractical evacuation capabilities shall be classified as Group R-4
occupancies, if serving six to 12 persons, or as Group R-3 occupancies, if
serving five or fewer persons. For purposes of this section, Standard No. 101
(1997) Chapter 22 is incorporated by reference, is not subject to frequent
change and is available at the State Law Library, 25 Rev. Dr. Martin Luther
King Jr. Blvd., St. Paul, Minnesota 55155.
SECTION 460
SUPERVISED LIVING FACILITIES
4604.1
Classification of supervised
living facilities. Supervised living facilities are classified in
accordance with Chapter 2 and must meet the fire safety requirements for the
designated occupancy classification.
4604.1.1
Class A-1 supervised living facilities. Class A-1 supervised
living facilities must meet Group R-3 occupancy requirements.
4604.1.2
Class A-2 supervised living
facilities. Class A-2 supervised living facilities housing not more than
16 persons, excluding staff, must meet Group R-4 occupancy requirements. Class
A-2 supervised living facilities housing more than 16 persons, excluding staff,
must meet Group I-1 occupancy requirements.
4604.1.3
Class B-1 supervised living
facilities. Class B-1 supervised living facilities meeting the
fire-protection provisions of Chapter 21 of the National Fire Protection
Association Standard No. 101 (Quincy, Massachusetts, 1985) for impractical
evacuation capabilities shall be classified as Group R-3 occupancies. For the
purposes of Sections 4604.1.3 and 4604.1.4, Standard No. 101 (1985) Chapter 21
is incorporated by reference, is not subject to frequent change and is
available at the State Law Library, 25 Rev. Dr. Martin Luther King Jr. Blvd.,
Saint Paul, Minnesota 55155.
4604.1.4
Class B-2 supervised living
facilities. Class B-2 supervised living facilities meeting the
fire-protection provisions of Chapter 21 of the National Fire Protection
Association Standard No. 101 (Quincy, Massachusetts, 1985) for impractical
evacuation capabilities shall be classified as Group R-4 occupancies.
4604.1.5
Class B-3 supervised living
facilities. Class B-3 supervised living facilities must meet Group I-2
occupancy requirements.