Minn. R. agency 151, ch. 7511, pt. 7511.8100 - CHAPTER 81 - ADULT DAY SERVICES CENTERS, RESIDENTIAL HOSPICE FACILITIES AND SUPERVISED LIVING FACILITIES
The IFC is amended by adding Chapter 81 to read:
CHAPTER 81
ADULT DAY SERVICES CENTERS, RESIDENTIAL HOSPICE FACILITIES AND SUPERVISED LIVING FACILITIES
SECTION 8101
GENERAL
8101.1
Requirements. Adult day
services centers, residential hospice facilities and supervised living
facilities shall meet the requirements of this chapter.
SECTION 8102
ADULT DAY SERVICES CENTERS
8102.1
Classification of adult day
services centers. Adult day services centers are classified in
accordance with the following and must meet the fire safety requirements for
the designated occupancy classification.
8102.1.1
Serving only participants
capable of self-preservation. Centers serving only participants who are
capable of taking appropriate action for self-preservation under emergency
conditions shall meet all applicable requirements for Group E
occupancies.
8102.1.2
Serving
only participants not capable of self-preservation. Centers serving only
participants who are not capable of taking appropriate action for
self-preservation under emergency conditions shall meet all applicable
requirements for Group I-4 occupancies.
8102.1.3
Serving both participants
capable and participants not capable of self-preservation. Centers
serving a population that includes both participants who are capable and
participants who are not capable of taking appropriate action for
self-preservation under emergency conditions shall meet the occupancy
requirements for Group I-4 or Group E occupancies. In addition to the
requirements for Group E occupancies, the center shall meet the requirements
set forth in Sections 8102.1.3.1 through 8102.1.3.4.
8102.1.3.1
Population. Not more
than 50 percent of the centers licensed capacity shall be made up of
participants who are not capable of taking appropriate action for
self-preservation under emergency conditions.
8102.1.3.2
Location. The center
must be located on a floor level with all exits directly to grade without any
intervening stairs.
8102.1.3.3
Fire alarm and detection. The center shall be protected with a
complete automatic fire alarm system consisting of automatic smoke detection in
all corridors and at the top of all stairways and automatic detection in boiler
and furnace rooms, kitchens, storage rooms, custodial closets, laundries, and
other hazardous areas.
8102.1.3.4
Evacuation time. The center shall demonstrate the ability to
evacuate the entire population of the center within three minutes.
SECTION 8103
RESIDENTIAL HOSPICE FACILITIES
8103.1
Classification of residential hospice facilities. Residential
hospice facilities meeting the fire-protection provisions of Chapter 32 of NFPA
Standard No. 101 (Quincy, Massachusetts, 2012) for impractical evacuation
capabilities shall be classified as Group R-4 occupancies, if serving six to 12
persons, or as Group R-3 occupancies, if serving five or fewer persons. For
purposes of this section, Standard No. 101 (2012) Chapter 32 is incorporated by
reference, is not subject to frequent change and is available at the State Law
Library, 25 Rev. Dr. Martin Luther King Jr. Blvd., St. Paul, Minnesota 55155.
SECTION 8104
SUPERVISED LIVING FACILITIES
8104.1
Classification of supervised
living facilities. Supervised living facilities are classified in
accordance with Chapter 2 and must meet the fire safety requirements for the
designated occupancy classification.
8104.1.1
Class A-1 supervised living facilities. Class A-1 supervised
living facilities must meet Group R-3 occupancy requirements.
8104.1.2
Class A-2 supervised living
facilities. Class A-2 supervised living facilities housing not more than
16 persons, excluding staff, must meet Group R-4 occupancy requirements. Class
A-2 supervised living facilities housing more than 16 persons, excluding staff,
must meet Group I-1 occupancy requirements.
8104.1.3
Class B-1 supervised living
facilities. Class B-1 supervised living facilities meeting the
fire-protection provisions of Chapter 32 of NFPA Standard No. 101 (Quincy,
Massachusetts, 2012) for impractical evacuation capabilities shall be
classified as Group R-3 occupancies. For the purposes of Sections 8104.1.3 and
8104.1.4, Standard No. 101 (2012) Chapter 32 is incorporated by reference, is
not subject to frequent change and is available at the State Law Library, 25
Rev. Dr. Martin Luther King Jr. Blvd., Saint Paul, Minnesota 55155.
8104.1.4
Class B-2 supervised living
facilities. Class B-2 supervised living facilities meeting the
fire-protection provisions of Chapter 32 of NFPA Standard No. 101 (Quincy,
Massachusetts, 2012) for impractical evacuation capabilities shall be
classified as Group R-4 occupancies.
8104.1.5
Class B-3 supervised living
facilities. Class B-3 supervised living facilities must meet Group I-2
occupancy requirements.
Notes
Statutory Authority: MS s 299F.011; 326B.02