15 Miss. Code. R. 15-77-1-5.1.9 - Septic Tank Sizing

The effective liquid capacity of septic tanks for dwellings shall be based on the number of bedrooms proposed or anticipated as shown in the table below:

Number of Bedrooms Number of Occupants Minimum Effective Liquid Capacity (gallons) without baffle or effluent filter Minimum Effective Liquid Capacity (gallons) with baffle or effluent filter
2 or less 4 or less 750 750
3 6 900 900
4 8 1200 1000
5 10 1500 1250
6 12 1800 1500

For each additional bedroom add 260 gallons

For each additional occupant over 2 per bedroom add 130 gallons

For a nonresidential application, the septic tank will be sized at twice the estimated daily flow