15 Miss. Code. R. 18-77-5.1.6 - Minimum Standards for Septic Tank Construction
1. General
a. All septic tanks manufactured for sale in
the state of Mississippi shall bear an imprint identifying the manufacturer,
the serial number assigned to the manufacturer's plans and specifications
approved by the Department, the liquid or working capacity of the tank and be
marked with the date of manufacture. These imprints and markings must be
visible at the time of inspection by the Department.
b. All openings and lids shall be capable of
being sealed in a way that will prevent entrance of surface water and
groundwater.
c. Tank openings shall
be securely fastened or sealed to prevent unwarranted access to the contents of
the tanks vandal, tamper and child resistant. Acceptable protection of openings
may include, but is not limited to:
i. A
padlock
ii. An "O" ring with twist
lock cover requiring special tools for removal
iii. Covers weighing sixty-five (65) pounds
or more, net weight
iv. Stainless
steel or other corrosion resistant fasteners for fiberglass or polyethylene
lids.
2.
Prefabricated Concrete Septic Tank
a. A
minimum twenty-eight (28) -day concrete compressive strength of three thousand
(3,000) pounds per square inch must be used in the construction of the septic
tank. The concrete must achieve a minimum compressive strength of two thousand
five hundred (2,500) pounds per square inch before removal of the tank for the
manufactured site. It shall be the responsibility of the manufacturer to
certify that this condition has been met before shipment. Accelerated curing in
the mold by use of propane gas or other fuels is prohibited, except by accepted
methods and upon approval of the Department.
b. Lids, walls and bottom thickness must be a
minimum of three (3) inches. The bottom and walls must be a monolithic pour.
3. Steel Septic Tanks
a. Steel septic tanks must meet Underwriter's
Laboratory Standard UL-70 for the tank coating. Only tanks listed as approved
under the current published listing will be approved for installation.
4. Fiberglass and
Polyethylene Septic Tanks
a. Resins and
sealants used in the tank manufacturing process shall be capable of effectively
resisting the corrosive influences of the liquid components of sewage, sewage
gases and soil burial. Materials used shall be formulated to withstand shock,
vibration, normal household chemicals, earth and hydrostatic pressure when
either full or empty.
b. Not less
than thirty (30) percent of the total weight of the tank shall be fiberglass
reinforcement. Fiberglass tanks with an effective liquid capacity of not over
one thousand five hundred (1,500) gallons shall have a minimum wall thickness
of 1/4 inch. However, a wall thickness of not less than 3/16 inch will be
allowed in small isolated areas of a tank.
c. Internal surfaces shall be coated with an
appropriate gel coating to provide a smooth, porefree, watertight surface.
d. Tanks shall be constructed so
that all parts of the tank meet the following mechanical requirements:
i. Ultimate tensile strength - minimum twelve
thousand (12,000) PSI when tested in accordance with ASTM D 638-89, Standard
Method of Test for Tensile Properties of Plastics.
ii. Flexural strength - minimum nineteen
thousand (19,000) PSI when tested in accordance with D 790-86, Standard Method
of Test for Flexural Properties of Unreinforced and Reinforced Plastics and
Electrical Insulating Materials.
iii. Flexural modules of elasticity - minimum
eight hundred thousand (800,000) PSI when tested in accordance with ASTM D
790-86 , Standard Method of Test for Flexural Properties of Unreinforced and
Reinforced Plastics and Electrical Insulating Materials.
e. A test report from an independent testing
laboratory is required to substantiate that individual tank design and material
formulations meet the requirements of Rule 5.1.6.4.d.