15 Miss. Code. R. 18-77-5.1.9 - Septic Tank Sizing
The effective liquid capacity of septic tanks for dwellings shall be based on the number of bedrooms proposed or anticipated as shown in the table below:
|
Number of Bedrooms |
Number of Occupants |
Minimum Effective Liquid Capacity (gallons) without baffle or effluent filter |
Minimum Effective Liquid Capacity (gallons) with baffle or effluent filter |
|
2 or less |
4 or less |
750 |
750 |
|
3 |
6 |
900 |
900 |
|
4 |
8 |
1200 |
1000 |
|
5 |
10 |
1500 |
1250 |
|
6 |
12 |
1800 |
1500 |
For each additional bedroom add 260 gallons
For each additional occupant over 2 per bedroom add 130 gallons
For a nonresidential application, the septic tank will be sized at twice the estimated daily flow