19 Miss. Code. R. 7-5.06.10.1 - Single-wide Factory-Built Homes
TABLE VI- MINIMUM NUMBER OF TIEDOWNS FOR WIND ZONE II*
|
Length of Factory-Built home, excluding draw bar (ft.) |
Number of vertical ties** |
Number of diagonal ties, each side |
Total required anchors per home |
|
0-40 |
5 |
5 |
10 |
|
41-60 |
7 |
7 |
14 |
|
61-84 |
9 |
9 |
18 |
TABLE VII- MINIMUM NUMBER OF TIEDOWNS FOR WIND ZONE I*
|
Length of Factory-Built home, excluding draw bar (ft.) |
Number of vertical ties *** |
Number of diagonal ties, each side |
Total required anchors per home **** |
|
0-40 |
0 |
4 |
8 |
|
41-60 |
0 |
6 |
12 |
|
61-84 |
0 |
8 |
16 |
* These tables are based on a minimum working load per tie of 3,150 lbs. with a 50 % overload (4,725 lbs. total).
** The Federal Manufactured home construction and safety standards require all Factory-Built homes designed to be located in wind Zone II and III to have a diagonal tie installed at each vertical tie location.
*** If existing vertical tie down straps or brackets are present on the home, vertical straps and anchors must be installed at these locations.
**** If the maximum support pier height is over 24 inches, an additional diagonal tie must be added, per side, for every additional 12 inches of pier height or a portion thereof.