N.H. Admin. Code § Lab 1403.56 - Spray Finishing Operations
The employer shall ensure compliance with the following requirements:
(a) In conventional dry
type spray booths, over-spray dry filters or filter rolls shall ensure an
average air velocity over the face of the booth of not less than 100 linear
feet per minute;
(b) Electrostatic
spraying operations shall be conducted with an air velocity of not less than 60
linear feet per minute, or more, depending on the volume of the finishing
material being applied and its flammability and explosion characteristics
;
(c) Visible gauges or an audible
alarm or pressure-activated devices shall be installed to indicate or ensure
that the required air velocity is maintained;
(d) Filter pads shall be inspected, and
clogged filter pads discarded, and replaced. Filter rolls shall be inspected to
ensure proper replacement of filter media;
(e) Spray booths shall be so installed that
all portions are readily accessible for cleaning;
(f) A clear space of not less than 3 feet on
all sides of a spray booth shall be kept free from storage or combustible
construction;
(g) There shall be no
open flame or spark producing equipment in any spraying area nor within 20 feet
thereof, unless separated by a partition capable of stopping vapor
travel;
(h) Electrical wiring and
equipment not subject to deposits of combustible residues but located in a
spraying area shall be of explosion proof type;
(i) The quantity of flammable or combustible
liquids kept in the vicinity of spraying operations shall be the minimum
required for operations and shall not exceed a supply for one day or one
shift;
(j) Whenever flammable or
combustible liquids are transferred from one container to another, both
containers shall be bonded and grounded to prevent discharge sparks of static
electricity;
(k) All spraying areas
shall be kept as free from the accumulation of deposits of combustible residues
as practical, with cleaning conducted daily if necessary. Scrapers, spuds, or
other such tools used for cleaning purposes shall be of nonspark
material;
(l) Residue scrapings and
debris contaminated with residue shall be immediately removed from the
premises; and
(m) "No Smoking"
signs in large letters on contrasting color background shall be conspicuously
posted at all spraying areas and paint storage rooms.
Notes
#4118 eff 8-22-86, EXPIRED: 8-22-92
New. #6684, eff 2-4-98, EXPIRED: 2-4-06
New. #8606, INTERIM, eff 4-12-06, EXPIRED: 10-09-06 (formerly Lab 1403.70)
New. #8796, eff 1-11-07 (from Lab 1403.60)
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.