N.J. Admin. Code § 12:90-5.13 - Shop inspection of unfired pressure vessels
(a) Shop inspection
of unfired pressure vessels shall be required, except as provided in (b)
below.
(b) Unfired pressure vessels
in which steam is not generated, and which do not exceed the following volume
and pressure limits, may be exempted from shop inspections by qualified
inspectors; provided, that they comply in all other respects with this
subchapter:
1. Five cubic feet in volume and
250 psig design pressure;
2. One
and one-half cubic feet in volume and 600 psig design pressure.
(c) Such vessels shall be of
simple, single wall chamber construction.
(d) Vessels exempted from ASME Code
inspection by this section shall be stamped with the "UM" symbol, or as
otherwise provided for construction other than Class I pressure
vessel.
(e) Shell and tube heat
exchangers, jacketed vessels and other type vessels which may be subject to
differential pressures shall be shop inspected by an authorized
inspector.
Notes
See: 21 New Jersey Register 3247(a), 22 New Jersey Register 235(a).
Stylistic changes.
Amended by R.1996 d.588, effective
See: 28 New Jersey Register 4060(a), 28 New Jersey Register 5224(a).
Added (f).
Amended by R.1999 d.304, effective
See: 31 New Jersey Register 1556(a), 31 New Jersey Register 2604(b).
Deleted a former (f).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.