N.M. Admin. Code § 14.10.4.14 - CHAPTER 4 EQUIPMENT FOR GENERAL USE

Article 422 Appliances. See this article of the NEC and add the following to section 422.19. evaporative cooling units where an evaporative cooler is installed, a listed raceway shall be installed during rough-in from the control point to the evaporative cooler location. The raceway shall contain a wire-type equipment-grounding conductor from the control point outlet box to the junction box at the unit. The equipment grounding conductor shall be sized in accordance with table 250.122

Notes

N.M. Admin. Code § 14.10.4.14
14.10.4.14 NMAC - Rp, 14.10.4.14 NMAC, 6-28-13, Adopted by New Mexico Register, Volume XXXIV, Issue 04, February 28, 2023, eff. 3/28/2023