N.M. Admin. Code § 14.7.2.17 - CHAPTER 9 - FIRE PROTECTION SYSTEMS
See this chapter of the IBC except as provided below.
A.
Section 903 - Automatic Sprinkler
Systems. See this section of the IBC except as provided below.
Section 903.2 - Where required. See this section of the IBC except
delete the exception.
B.
Section 909 - Smoke Control Systems. See this section of the IBC
except as provided below.
(1)
Section
909.8 - Exhaust method. See this section of the IBC except as provided
below. Section 909.8.1 - Smoke layer. Delete this section of the
IBC and substitute with the following: The height of the lowest horizontal
surface of the accumulating smoke layer shall be maintained at least six feet
(1829 mm) above any walking surface which forms a portion of a required egress
system within the smoke zone. The required exhaust rate for the zone shall be
the largest of the calculated plume mass flow rates for the possible plume
configurations. Provisions shall be made for a natural or mechanical supply of
air from outside or adjacent smoke zones to make up for the air exhausted.
Makeup airflow rates, when measured at the potential fire locations shall not
increase the smoke production rate beyond the capabilities of the smoke control
system. The temperature of the makeup air shall be such that it does not expose
temperature-sensitive fire protection systems beyond their limits.
(2)
Section 909.9 - Design fire.
Delete this section of the IBC and substitute with the following. The design
fire shall be based on a rational analysis performed by a registered design
professional and approved by the building official. The design fire shall be
based on the analysis in accordance with Section 909.4 and this
section.