N.M. Admin. Code § 14.7.2.25 - CHAPTER 17 - SPECIAL INSPECTIONS AND TESTS
See this chapter of the IBC except as provided below.
A.
Section 1705.3 - Concrete
Construction. See this section of the IBC except as provided below.
(1)
Subsection 2 - Delete this
section of the IBC and substitute: continuous concrete footings supporting
walls of buildings three stories or less in height that are fully supported on
earth or rock;
(2)
Subsection
3 - Delete this section of the IBC and substitute: nonstructural
concrete slabs supported directly on the ground, except pre-stressed
slabs-on-grade;
(3)
Subsection 4 - Delete this section of the IBC with no
substitution.
B.
Section 1705.4 - Masonry Construction. See this section of the IBC
except delete Exception 2.
C.
Section 1705.18 - Fire-resistant penetrations and joints. Delete
this section of the IBC and substitute with the following: In buildings three
stories or greater, in buildings to Risk Category III and IV, or in fire areas
containing Group R occupancies with an occupant load greater than 200, special
inspections for through-penetrations, membrane penetration firestops,
fire-resistant joint systems and perimeter fire containment systems that are
tested and listed in accordance with Sections 714.4.1.2, 714.5.1.2, 715.3.1 and
715.4 shall be in accordance with Section 1705.18.1 or 1705.18.2.