N.M. Admin. Code § 14.7.3.28 - [Effective 1/13/2025] APPENDIX AQ TINY HOUSES
Delete this section of the IRC and substitute with the following sections.
A.
Section
AQ101 General. Section AQ101.1 Scope. This appendix shall be applicable
to tiny houses used as single dwelling units providing complete independent
living facilities for one or more persons, including permanent provisions for
living, sleeping, eating, cooking, and sanitation and placed on a permanent
foundation. Tiny houses shall comply with this code except as otherwise stated
in this appendix. Tiny houses constructed in New Mexico or constructed outside
New Mexico and transported into New Mexico shall be inspected to comply with
New Mexico Residential Code requirements for instate or out of state production
of dwelling units. This shall include Appendix Q of the New Mexico Residential
Code. Tiny houses constructed on a chassis with permanent axle shall be
considered recreational vehicles and shall meet codes for and be licensed as
recreational vehicles so long as the axle remains in place. If axles are
removed and the unit placed on supports (foundation) the unit must comply with
code requirements for tiny houses placed on a permanent foundation. Tiny houses
placed upon a permanent foundation shall be constructed to comply with New
Mexico Building Residential Codes including Appendix AQ (Tiny Houses) of the
IRC.
B.
Section AQ102
Definitions. Section AQ102.1 General Definitions. The following words
and terms shall, for the purposes of this appendix, have the meanings shown
herein. Refer to Chapter 2 of the IRC for general definitions.
(1)
Emergency egress. A
skylight, roof window, or other emergency egress opening designed and installed
to satisfy the emergency escape and rescue opening requirements in Section
R310.2.
(2)
Landing
platform. A landing measuring two treads deep and two risers tall,
provided as the top step of a stairway or ladder accessing a loft.
(3)
Loft. A floor level located
more than 30 inches (762 mm) directly above the main floor and open to the main
floor on at least one side with a ceiling height of less than 6 feet 8 inches
(2032 mm), used as a living or sleeping space. The total area of all lofts
shall not exceed 40 percent of the floor area.
(4)
Tiny house. A dwelling that
is 400 square feet (37 m2) or less in floor area excluding lofts and does not
include recreational vehicles.
C.
Section AQ103 Ceiling height.
AQ103.1 Minimum ceiling height. Habitable space and hallways in tiny
houses shall have a ceiling height of not less than 6 feet 8 inches (2032 mm).
Bathrooms, toilet rooms, and kitchens shall have a ceiling height of not less
than 6 feet 4 inches (1930 mm). Obstructions shall not extend below these
minimum ceiling heights including beams, girders, ducts, lighting, and other
obstructions. Exception: Ceiling heights in lofts are permitted to
be less than 6 feet 8 inches (2032 mm).
D.
Section AQ104 Lofts.
(1)
Section AQ104.1 Minimum loft area
and dimensions. Lofts used as a sleeping or living space shall meet the
minimum area and dimension requirements of Sections AQ104.1.1 through
AQ104.1.3.
(a)
Section AQ104.1.1 Minimum
area. Lofts shall have a floor area of not less than 35 square feet
(3.25 m2).
(b)
Section
AQ104.1.2 Minimum dimensions. Lofts shall be not less than 5 feet (1524
mm) in any horizontal dimension.
(c)
Section AQ104.1.3 Height effect on
loft area. Portions of a loft with a sloping ceiling measuring less than
3 feet (914 mm) from the finished floor to the finished ceiling shall not be
considered as contributing to the minimum required area for the loft.
Exception: Under gable roofs with a minimum slope of 6:12.
portions of a loft with a sloping ceiling measuring less than 16 inches (406
mm) from the finished floor to the finished ceiling shall not be considered as
contributing to the minimum required area for the loft.
(2)
Section AQ104.2 Loft access.
The access to and primary egress from lofts shall be any type described in
Sections AQ104.2.1 through AV104.2.4.
(a)
Section AQ104.2.1 Stairways. Stairways accessing lofts shall
comply with this code or with Sections AQ104.2.1.1 through AQ104.2.1.5.
(i)
Section AQ104.2.1.1 Width.
Stairways accessing a loft shall not be less than 17 inches (432 mm) in clear
width at or above the handrail. The minimum width below the handrail shall be
not less than 20 inches (508 mm).
(ii)
Section AQ104.2.1.2
Headroom. The headroom in stairways accessing a loft shall be not less
than 6 feet 2 inches (1880 mm) as measured vertically from a sloped line
connecting the tread or landing platform nosings in the middle of their
width.
(iii)
Section
AQ104.2.1.3 Treads and risers. Risers for stairs accessing a loft shall
be not less than 7 inches (178 mm) and not more than 12 inches (305 mm) in
height. Tread depth and riser height shall be calculated in accordance with one
of the following formulas:
(a) The tread
depth shall be 20 inches (508 mm) minus 4/3 of the riser height.
(b)The riser height shall be 15 inches (381
mm) minus 3/4 of the tread depth.
(iv)
Section AQ104.2.1.4 Landing
platforms. The top tread and riser of stairways or ladders accessing
lofts shall be constructed as a landing platform where the loft ceiling height
is less than 6 feet 2 inches (1880 mm) at the point where the stairway or
ladder meets the loft.
(v)
Section AQ104.2.1.5 Handrails. Handrails shall comply with Section
R311.7.8.
(vi)
Section
AQ104.2.1.6 Stairway guards. Guards at open sides of stairways shall
comply with Section R312.1.
(b)
Section AQ104.2.2 Ladders.
Ladders accessing lofts shall comply with Sections AQ104.2.1 and AQ104.2.2,
including the requirements for handrails in section R311.7.8, and R308.4.6
glazing adjacent to stairs and ramps, and shall be permanently attached to the
loft structure by a device that prevents movement during use. Attachment shall
not be accomplished by use of toenails or nails subject to withdrawal.
(i)
Section AQ104.2.2.1 Size and
capacity. Ladders accessing lofts shall have a rung width of not less
than 12 inches (305 mm) and rungs shall be spaced with 10 inches (254mm)
minimum to 14 inches (356mm) maximum spacing between rungs. Floor decking of
lofts accessed by ladders shall be no more than 81/2 feet above the main level
floor. Ladders shall be capable of supporting a 200-pound (75 kg) load on any
rung. Rung spacing shall be uniform within 3/8-inch (9.5 mm).
(ii)
Section AQ104.2.2.2
Incline. Ladders shall be installed at 70 to 80 degrees from
horizontal.
(c)
Section AQ104.2.3 Alternating tread devices. Alternating tread
devices accessing lofts shall comply with Sections R311.7.11 1 and R311.7.11.2.
The clear width at and below the handrails shall be not less than 20 inches
(508 mm).
(d)
Section
AQ104.2.4 Ships ladders. Ships ladders accessing lofts shall comply with
Sections R311.7.12.1 and R311.7.12.2. The clear width at and below handrails
shall be not less than 20 inches (508 mm).
(e)
Section AQ104.2.5 Loft
Guards. Loft guards shall be located along the open side of lofts. Loft
guards shall not be less than 36 inches (914 mm) in height or one-half of the
clear height to the ceiling, whichever is less.
E.
Section AQ105 Emergency escape and
rescue openings: AQ105.1 General. Tiny houses shall meet the
requirements of Section R310 for emergency escape and rescue openings including
lofts of 35 square feet or greater. Egress roof access windows in lofts shall
be deemed to meet the requirements of Section R310 when installed with the
bottom of their opening no more than 44 inches (1118 mm) above the loft
floor.