N.M. Admin. Code § 14.7.4.22 - ELECTRICAL
A.
Electrical
system installation. Electrical wiring shall pass through a channel or
conduit. Approved rigid or flexible electrical conduit shall withstand ramming
pressures without damage or collapse. Electrical wiring within a channel shall
be covered a minimum of one and one-fourth inches. Prior to ramming, a minimum
five inch earth cover shall be provided over any horizontal pipe.
B.
UF cable installation. UF
cable may not be rammed within the rammed earth wall. Exception: UF cable
installed within an approved conduit or channel. In a channel installation, UF
cable must be covered a minimum of one and one-fourth inches with plaster,
adobe or similar finish.
C.
Electrical box installation. Plastic electrical boxes shall not be
rammed within the rammed earth wall. Exception: plastic electrical boxes
installed in a channel installation.