N.M. Admin. Code § 8.370.16.75 - NURSE CALL SYSTEM

A nurse call station shall be installed at each resident's bed, in each resident's toilet room, and at each bathtub and shower. The nurse call at the toilet, bath, and shower rooms shall be an emergency call equipped with pull cords of sufficient length to extend to within 18 inches off the floor. All calls shall register at the nurse station and shall actuate a visible signal in the corridor where visibility to corridors is obstructed at the room door. In multi-corridor nursing units, additional visible signals shall be installed at corridor intersections. An emergency call station shall also be provided in any enclosed room used by residents.

Notes

N.M. Admin. Code § 8.370.16.75
Adopted by New Mexico Register, Volume XXXV, Issue 12, June 25, 2024, eff. 7/1/2024