N.M. Admin. Code § 8.370.18.47 - HEATING, VENTILATION AND AIR CONDITIONING
A. Heating, air conditioning, piping,
boilers, and ventilation equipment must be furnished, installed and maintained
to meet all requirements of current state and local mechanical, electrical, and
construction codes.
B. The heating
method used by the facility must have a minimum indoor-winter-design capacity
of 75 degrees farenheit with controls provided for adjusting temperature as
appropriate for patient and staff comfort.
C. The use of unvented heaters, open flame
heaters or portable heaters is prohibited.
D. An ample supply of outside air must be
provided in all spaces where fuel fired boilers, furnaces, or heaters are
located to assure proper combustion.
E. All fuel fired boilers, furnaces, or
heaters must be connected to an approved venting system to take the products of
combustion directly to the outside air.
F. A facility must be adequately ventilated
at all times to provide fresh air and the control of unpleasant
odors.
G. All gas-fired heating
equipment must be provided with a one-hundred percent automatic cutoff control
valve in event of pilot failure.
H.
The facility must be provided with a system for maintaining patients and
staff's comfort during periods of hot weather.
I. All boiler, furnace or heater rooms shall
be protected from other parts of the building by construction having a fire
resistance rating of not less than one hour. Door must be self-closing with 3/4
hour fire resistance.
J. Operating
room supply air shall be provided from ceiling outlets near the center of the
work area. Return air from floor level with at least two return inlets located
as remote as possible shall be provided.
K. All central ventilation and air condition
systems shall be provided filters having efficiencies greater than twenty-five
percent. Operating rooms shall have ninety percent filter
efficiencies.