N.M. Admin. Code § 8.371.2.40 - HEATING, VENTILATION AND AIR CONDITIONING
A. Heating, air-conditioning, piping,
boilers, and ventilation equipment must be furnished, installed and maintained
to meet all requirements of current state and local mechanical, electrical, and
construction codes. All facilities must have documentation that fuel-fire
heating systems have been checked, tested and maintained annually by qualified
personnel.
B. The heating method
used by the facility must provide a minimum temperature of 70 degrees farenheit
in all rooms used by the clients.
C. An ample supply of outside air for proper
combustion must be provided in all spaces where fueled fired boilers or heaters
are located.
D. All gas fired
heating equipment must be provided with a one hundred percent automatic cutoff
control valve in event of pilot failure.
E. Each building where gas is used must have
an outside gas shutoff valve. The facility must have a tool readily available
which will operate the shut-off valve. All personnel employed by the facility
must be instructed as to location of the shut-off valve and tool and must know
how to shut off the gas supply in case of fire or gas leakage.
F. No open-face gas or electric heater nor
unprotected single shell gas or electric heating device shall be used for
heating the facility. Portable heating units shall not be used for heating the
facility.
G. All boiler, furnace or
heater rooms shall be protected from other parts of the building by
construction having a fire resistance rating of not less than one-hour. Doors
to these rooms shall be 1-3/4" solid core.
H. A facility must be adequately ventilated
at all times to provide fresh air and the control of unpleasant odors by either
mechanical or natural means.
I. All
gas burning heating and cooking equipment must be connected to an approved
venting system to take the products of combustion directly to the outside
air.
J. All openings to the outer
air used for ventilation must be screened with screening material of not less
than 16 meshes per lineal inch.
K.
Screen doors must be equipped with self-closing devices.
L. A facility must be provided with a system
for maintaining residents comfort during periods of hot
weather.