10A N.C. Admin. Code 13K .1209 - HOSPICE INPATIENT REQUIREMENTS FOR GENERAL ELECTRICAL
(a) All main water supply shut off valves in
the sprinkler system shall be electronically supervised so that if any valve is
closed an alarm will sound at a continuously manned central station.
(b) No two adjacent emergency life safety
branch lighting fixtures shall be on the same circuit.
(c) Receptacles in bathrooms shall have
ground fault protection.
(d) Each
patient bed location shall be provided with a minimum of eight single or four
duplex receptacles.
(e) Each
patient bed location shall be supplied by at least two branch circuits, one
from the equipment branch and one from the normal system.
(f) The fire alarm system shall be installed
to transmit an alarm automatically to the fire department that is legally
committed to serve the area where the facility is located, by the direct and
reliable method approved by local ordinances.
(g) In patient areas, fire alarms shall be
gongs or chimes rather than horns or bells.