Ohio Admin. Code 3352-7-25 - Fire safety plan
(A)
General policy.
(1)
Fire safety
standards promulgated by the occupational safety and health administration are
contained in 29 Code of Federal Regulations, part 1910.38, fire prevention, and
in subpart L, 29, Code of Federal Regulations 1910.155.165, fire detection,
alarms and suppression. The standards mandate that Wright state university
develop and implement a fire safety plan that includes:
(a)
Determining the
response level to incipient stage fires.
(b)
Developing a plan
based on selected response level.
(c)
Maintaining fire
detection, alarm, and suppression systems.
(2)
This policy
applies to university employees at the Dayton campus, lake campus, Yellow
Springs family health center, Cox institute, Duke E. Ellis institute, Eugene W.
Kettering center, Wright state university research center, and university
operations at affiliated hospitals.
(3)
University
employees are required to read and understand the contents of the university
fire safety plan and to take appropriate action in the event of a fire
emergency in any university facility.
(B)
Definitions.
(1)
A university employee is any faculty, staff, or student
employee who receives compensation from the university for his/her employment
and who is covered under Ohio bureau of workers compensation.
(2)
An incipient
stage fire is a fire in the initial or beginning stage that can be controlled
by using a portable fire extinguisher and that does not require using
protective equipment.
(3)
An area of rescue assistance is a designated area of
protection on floors of a building above ground level where an individual who
physically cannot use the stairways for evacuation is to wait for rescue
assistance. All areas of rescue assistance shall be readily
identifiable.
(4)
Designated personnel are university employees who have
received annual training on the proper use of portable fire
extinguishers.
(C)
Response level.
(1)
The occupational
safety and health administration provides three options for the response level
to incipient stage fires.
(a)
Option A requires all employees to evacuate the
workplace when a fire alarm sounds.
(b)
Option B provides
portable fire extinguishers and designates certain employees to use them to
fight incipient stage fires.
(c)
Option C provides
portable fire extinguishers and permits all employees to fight incipient stage
fires.
(2)
Dayton campus, lake campus, Yellow Springs family
health center, Cox institute, Duke E. Ellis institute, Eugene W. Kettering
center, and Wright state university research center.
(a)
The university
has elected to exercise the occupational safety and health administration
option B whereby university personnel, on a voluntary basis, are designated to
fight incipient stage fires. Designated personnel are employees of the
departments of environmental health and safety, parking and transportation,
physical plant, and public safety; staff at the Ervin J. Nutter center;
academic/research laboratory supervisors; and, university employees in select
specialty work areas.
(b)
By electing to exercise the occupational safety and
health administration option B, the university has provided a copy of the
university fire safety plan to each employee and has instructed all employees
not designated in paragraph (C)(2)(a) of this rule that they must take no
action to fight an incipient stage fire and must evacuate a building
immediately when a fire alarm sounds.
(3)
School of
medicine facilities operations at the veterans affairs medical center and
university operations at other affiliated hospitals.
(a)
Wright state
university employees working at the veterans affairs medical center and other
affiliated hospitals are to follow the instructions outlined in the fire safety
plans of those institutions.
(b)
If a university
employee working at the veteran affairs medical center or another affiliated
hospital has not volunteered to fight incipient stage fires and has not
received specified training in using portable fire extinguishers, he/she is
required to evacuate a building immediately when a fire alarm
sounds.
(D)
Emergency action
plan.
(1)
All
university employees must be notified of the elements of the emergency action
plan contained in the university fire safety plan. All university employees are
required to fulfill those elements.
(2)
All employees are
expected to read and understand the information presented in the emergency
action plan, particularly their responsibilities regarding identifying building
exits and knowing when to activate a fire alarm and what action to take
following activation of an alarm, that is, identifying to the responding
emergency response personnel the location of the alarm station activated and
the location of the fire/smoke.
(E)
Emergency action
plan, employee responsibilities.
(1)
Fighting incipient stage fires in university buildings.
If a university employee is not a designated employee who has received the
required training in using portable fire extinguishers, he/she is responsible
for activating the nearest fire alarm and immediately exiting the building in
the event of a suspected or observed fire. Under no circumstances should the
employee attempt to extinguish the fire.
(2)
Emergency
procedures and escape route assignment. University employees are responsible
for determining the location of the closest exit from the work area that leads
outside the building and that is the primary emergency exit. University
employees also are responsible for determining the location of the secondary
exit from the work area, in the event that the primary exit is not accessible.
All outer doors will be marked as an exit.
(3)
Procedures to be
followed by employees who remain in a building to conduct critical plant
operations. Employees who are required and permitted by the responding fire
department to remain in a building to conduct critical plant operations should
perform their duties only if they are not in the smoke/fire area. Employees
should never risk injury when performing work related duties.
(4)
Procedures to
account for all employees after an emergency evacuation has been completed.
Supervisors or employees in lead positions are required to develop a procedure
to account, to the maximum degree possible, for all employees, students, and
visitors after an emergency evacuation has been completed. The procedure should
designate an area outside the building to which employees, students, and
visitors should report during an emergency evacuation.
(5)
Rescue and
medical duties. Rescue and medical treatment for injured employees will be
provided by the responding fire department. On the Dayton campus, Wright state
university police officers will assist responding fire department
personnel.
(6)
Preferred means for reporting fires. The preferred
means for reporting a fire is by using the fire alarm system in a building. As
quickly as possible after activating a fire alarm, employees are responsible
for meeting responding police officers and/or fire department personnel and
identifying the location of the alarm activated and the location of smoke
and/or fire.
(7)
Safe and orderly evacuation of building occupants. The
following procedures represent acceptable guidelines for ensuring the safe and
orderly evacuation of building occupants.
(a)
Building
occupants are not to use elevators.
(b)
Building
occupants are to use the primary emergency exit whenever accessible. When the
primary emergency exit is not accessible, building occupants are to use the
secondary emergency exit. Occupants evacuating the building should go
immediately to the designated meeting point away from the building. Supervisors
or employees in lead positions should account, to the maximum degree possible,
for employees, students, and visitors.
(c)
Building
occupants are to assist individuals with disabilities (nonwheelchair) in
exiting the building.
(d)
Building occupants who use wheelchairs and are on
floors above ground level are to go to the closest enclosed stairwell or to the
location in the building designated as the area of rescue assistance. A faculty
or staff member should remain with building occupants who use wheelchairs until
a rescue is completed or the emergency is terminated. Building occupants who
use wheelchairs and are located in the basement of buildings are to use the
tunnel system and go to the closest adjacent building not involved in the alarm
situation. No individuals, regardless of physical limitations, are to stay in
tunnels connected to the building in which the fire alarm has been
activated.
(e)
The responding fire department personnel or public
safety officers are to be informed as soon as possible of the number and
location of building occupants who use wheelchairs.
(f)
Building
occupants are not to reenter affected buildings until permitted to do so by
local fire department personnel or by the responding law enforcement
officers.
(F)
Emergency action
plan, building fire alarm system.
(1)
All university owned or leased facilities of general
occupancy, except the fine arts building, are equipped with fire alarm systems.
On the Dayton campus, the system feeds into the public safety communications
center. Personnel in the communications center are responsible for notifying
the Fairborn fire department, which has jurisdiction for the Dayton campus. At
all other campus locations, the fire department having jurisdiction is
notified, either directly or indirectly, of the activated
alarm.
(2)
Using a building fire alarm system normally is
restricted to situations where smoke and/or fire has been observed. In
situations where an odor, that is, chemical, electrical, and natural gas, is
detected, employees are to observe the following procedures.
(a)
Dayton
campus.
(i)
During normal work hours, eight-thirty a.m. until five p.m.,
employees on the Dayton campus are to notify the physical plant customer
service center. The customer service center is responsible for contacting the
department of environmental health and safety and appropriate physical plant
personnel who jointly will conduct a search of the area.
(ii)
Outside normal
work hours, employees on the Dayton campus are to notify the public safety
communications center. Outside normal work hours, an area search will be
conducted jointly by university police officers and physical plant maintenance
personnel.
(iii)
Responding personnel will determine the necessary
response and the immediate disposition of building occupants. Should evacuation
be necessary, instructions will be given over the university's public address
system and supplemented by verbal directions from on the scene emergency
response personnel.
(iv)
When fire and/or smoke is not evident, the emergency
response personnel, university police officers, environmental health and
safety, and physical plant, will activate the fire alarm system when they
determine that a fire is imminent and immediate evacuation is required and when
they determine that the alarm can be activated without danger of causing an
explosion. The alarm also will be activated at the instruction of the Fairborn
fire department. The decision to activate a building fire alarm system when
there is a detected odor but no visual sighting of fire and/or smoke will be
made only at the discretion of emergency response personnel.
(b)
Lake
campus, Yellow Springs family health center, Cox institute, Duke E. Ellis
institute, Eugene W. Kettering center, and Wright state university research
center.
(i)
During normal work hours, eighty-thirty a.m. until five
p.m., university employees will notify the building manager and/or maintenance
personnel of a detected odor, that is, chemical, electrical, and natural gas.
The building manager and/or maintenance personnel are responsible for
conducting a search of the building and for making the determination whether or
not to notify the designated fire department and to activate the fire alarm
system. If any questions arise as to the seriousness of the situation, the
building manager and/or maintenance personnel are not to hesitate in ordering
an immediate evacuation of the building. If there should be any concerns about
an explosive mixture from chemical or natural gas concentrations in the air,
the fire alarm is not to be activated.
(ii)
Outside normal
work hours, employees are responsible for notifying the designated fire
department and immediately evacuating the building.
(c)
Veterans affairs
medical center and other affiliated hospitals. University employees located at
the veterans affairs medical center and other affiliated hospitals are
responsible for following the procedures outlined in the fire safety plans of
those institutions. At no time should university employees place themselves or
others at risk. If any doubt arises as to the seriousness of the situation,
employees are to evacuate the building immediately.
(3)
Upon hearing a
building fire alarm, all occupants must evacuate the building immediately.
Faculty members and instructors are required to cease instruction and assist
students in exiting the building. The only exception for remaining in the
building applies to designated personnel, as defined in paragraph (C)(2)(a) of
this rule, who are required to operate or shut down critical systems. Should
smoke and/or fire be in the area of a critical system, designated personnel
also shall immediately evacuate the building and report to their respective
supervisors.
(4)
The individuals activating the fire alarm are
responsible, after evacuating the building, for meeting responding fire
department personnel and/or public safety officers and identifying the location
of the smoke and/or fire.
(5)
The Dayton campus and veterans affairs medical center
also utilize a public address system to announce the activation of a building
alarm system and to provide verbal instructions for exiting a building. The
public address system is the primary means for ordering evacuation from a
building for reasons other than smoke and/or fire.
(6)
University
personnel are to notify the maintenance department or the building owner of any
known areas within a building where the fire alarm appears not to be working or
cannot be heard over ambient noise. Any system that is not operating properly
is to be repaired immediately.
(7)
National and
local fire codes require that all manually operated pull stations be
unobstructed, conspicuous, and readily accessible.
(8)
It is the
responsibility of a building owner's maintenance personnel to ensure that the
fire alarm and public address systems are operational at all times. Any
questions regarding maintenance or testing of those systems can be directed to
the applicable maintenance department or to the Wright state university
department of environmental health and safety.
(G)
Training. The
information contained in paragraphs (D), (E), and (F) of this rule meets the
occupational safety and health administration requirements for training all
employees not designated to remain in a building and fight incipient stage
fires. The department of environmental health and safety will be the lead
department in identifying designated personnel and in completing initial and
refresher training in using portable fire extinguishers.
Replaces: 3352.03-7-25
Notes
Promulgated Under: 111.15
Statutory Authority: 3352.03
Rule Amplifies: 3352.03
Prior Effective Dates: 8/31/99, 8/31/01