Ohio Admin. Code 3701:1-52-10 - Fire protection
(A) The radiation room at a panoramic
irradiator must have heat and smoke detectors. The detectors must activate an
audible alarm. The alarm must be capable of alerting a person who is prepared
to summon assistance promptly. The sources must automatically become fully
shielded if a fire is detected.
(B) The radiation room at a panoramic
irradiator must be equipped with a fire extinguishing system capable of
extinguishing a fire without the entry of personnel into the room. The system
for the radiation room must have a shut-off valve to control flooding into
unrestricted areas.