Ohio Admin. Code 3701-28-12 - Construction and surface design of cisterns, reservoir tanks, hauled water storage tanks, and roof washers
(A)
Cisterns,
reservoir tanks, and hauled water storage tanks shall be watertight with a
reasonably smooth, clean interior surface. All concrete tanks shall be made of
materials and constructed in accordance with ASTM specifications C 913-2016.
All plastic or fiberglass tank materials shall meet NSF standard 61-2016. All
joints, connections, and other seams between component parts shall be sealed
with nontoxic waterproof material that meets NSF standard 61-2016 or equivalent
to prevent the loss of stored water and the infiltration of surface or ground
water.
(B)
Cisterns, reservoir tanks, and hauled water storage
tanks shall be easily accessible for cleaning. Partitions, baffles, or similar
structural features shall be constructed of nonabsorbent, easily cleanable
materials, free of spalls, cracks, or crevices which may entrap unwanted
matter.
(C)
The capacity of cisterns and hauled water storage tanks
shall be adequate to meet the intended needs of the household. No new cistern
of less than two thousand five hundred gallons capacity per dwelling unit shall
be installed. No new hauled water storage tank of less than one thousand
gallons capacity per dwelling unit shall be installed, except if the tank is a
supplemental water reservoir tanks for wells, ponds, and springs designed to
receive hauled water as an additional water source.
(D)
Inlets to
cisterns and hauled water storage tanks shall be of sufficient size and design
to dissipate the pressure of the influent stream and minimize the stirring of
any settled solids.
(E)
Cisterns, reservoir tanks, and hauled water storage
tanks shall be set level and at an adequate depth or location to prevent frost
heave. The bottom of the excavation shall be continuous, relatively smooth, and
free of rocks. The bottom of the excavation shall have a minimum of four inches
of material approved by the manufacturer of the tank. Tanks shall not bear on
rock ledges. Backfill shall be free of any large stones or debris, and shall be
placed in a manner consistent with tank manufacturer recommendations. Earth
cover shall be graded to prevent water from standing over the cistern or hauled
water storage tank.
(F)
Manholes or risers shall be sealed to the top of the
cistern or hauled water storage tank:
(1)
Concrete tanks
shall have an opening of a minimum diameter of twenty-four inches and shall be
constructed of the same or compatible material as the cistern or hauled water
storage tank.
(2)
Plastic tanks shall have an opening of a minimum
diameter of eighteen inches.
(3)
The manhole
opening shall have a watertight cover with edges projecting a minimum of eight
inches above the level of the surrounding surface. The edges of the manhole or
riser cover shall overlap the curb and project downward a minimum of two
inches. The covers shall be secured to minimize the danger of contamination,
accidents, and unwarranted entry.
(4)
A concrete patio
or wood deck may be located over a cistern or hauled water storage tank
provided that proper access is maintained for filling, service and
inspections.
(G)
A cistern shall be equipped with outlet drain or
overflow pipe. Outlet drains and overflow pipes are optional on hauled water
storage tanks. Cistern and hauled water storage tank outlet drains and overflow
pipes shall be a minimum of four inches in diameter and not be connected to any
sewer, soil pipe, building drain, or other waste pipe. Outlet drains and
overflow pipes shall be equipped with noncorroding animal guards with a maximum
opening of 0.43 inches. Such drains are to discharge at a point free from
flooding through an atmospheric break to prevent backflow.
(H)
Vents are
optional on cisterns and hauled water storage tanks with inlets and outlets
that are open to the air. Vents being utilized on a cistern or hauled water
storage tank shall be inverted, and the vents and other openings shall be
constructed and protected with noncorroding animal guards with a maximum
opening of 0.43 inches, so as to prevent the entrance of animals, insects, or
other contaminating material.
(I)
Fittings and
couplings which extend through the walls or the cover of cisterns and hauled
water storage tanks shall all be cast in place, by the manufacturer. Couplings
shall be made of cast brass, fiberglass, galvanized cast iron, flexible pipe to
manhole connectors conforming to ASTM C-923 2013, or shall be two piece
friction clamps or longitudinally ribbed plastic so as to prevent turning in
place and the entry of contamination or loss of stored water.
(J)
A minimum of one
above-ground roof washer/diverter and debris filtering device or a combination
type of device shall be provided on each cistern and for each one thousand five
hundred square feet of roof area. All roof areas being utilized for rainwater
capture shall be protected by a roof washer. All newly installed roof washers
shall be of a design that will automatically divert the first ten gallons of
rainfall runoff from the roof away from the cistern.
(1)
For the purposes
of this rule "roof washer" means any manual or automatic diverter or other
device that is designed to prevent the initial ten gallons of roof rainfall
from entering a cistern.
(2)
For the purposes of this rule "debris trap" means a
screened device or filter that removes larger debris such as leaves and twigs
after the water has discharged from the gutter and prior to entering a
cistern.
(3)
For the purposes of this rule "combination device"
means a device that functions as both a roof washer for the first ten gallons
and as a debris filter.
(4)
For the purposes of this rule "gutter guard" means any
device installed on the gutters designed to help exclude leaves and twigs from
entering the gutter.
(5)
The above-ground roof washer combination device or
filtering device shall be provided with an above grade and easily removable
debris trap with a minimum screen opening of one quarter inch. The debris trap
shall be installed prior to the filtering device and designed to catch or
entrap the larger debris before it enters the filter or cistern tank. The top
of the roof washer combination device or filtering device shall extend above
the ground a minimum of eight inches and have outlets of a minimum of four
inches. All collected rainwater shall pass through the roof washer combination
device or filtering device and the debris trap or combination device prior to
entering the cistern.
(6)
The debris filter or combination device shall have a
capacity of at least ten gallons for every fifteen hundred square feet of roof
area. Each debris filter or combination roof washer/filter device shall have
either several inches of one half inch to three-quarter inches of washed gravel
or an equivalent filtering media or filtering component capable of removing
larger particles.
(K)
Cistern and
hauled water storage tank inlet and fill pipes shall be a minimum diameter of
four inches, except where the inlet is from a well being used as a combination
water source with the cistern. Inlets shall be protected against contamination
at all times. The fill pipe shall be equipped with a secured and watertight cap
or cover and extend above the ground a minimum of eight inches. If an inlet
enters the cistern from a well being used as a combination water source, the
inlet from the well shall be protected by an air gap that is two times the
diameter of the inlet pipe above the cistern overflow level.
(L)
The water intake
for the pump in the cistern and hauled water storage tank closest to entering
the building shall at no time be located less than four inches from the bottom
of the cistern or hauled water storage tank. If multiple tanks are used for the
cistern or hauled water storage tank systems then this rule applies to the
intake for the tank closest to entering the building. The water intake for the
pump in the cistern and hauled water storage tank shall be one of the
following:
(1)
Be attached to a flotation device and be located a minimum of four inches below
the surface of the water;
(2)
Cast in place and shall be otherwise designed to
maintain the required depth settings in the water;
(3)
A submersible
pump located within the tank, not required to be attached to a flotation
device; or
(4)
A submersible pump located in a plastic casing next to
the tank, connected to the tank using a pitless adapter.
(M)
Water
obtained from cisterns shall be continuously disinfected and filtered as
prescribed in rule
3701-28-15 of the Administrative
Code. Hauled water storage tanks that receive hauled water from a public supply
as their only water source are not required to be provided with continuous
disinfection.
(N)
All new, repaired, or altered cisterns and hauled water
storage tanks shall be disinfected with chlorine or disinfection products
authorized by the department to neutralize contamination after construction,
installation, alteration, or repair, prior to water being removed for human
consumption.
(1)
The registered private water systems contractor
performing the construction, installation, alteration, or the person performing
the repair shall disinfect the private water system according to this rule at
the time of completion of the portion of work performed by that
person.
(2)
The owner of the private water system shall provide
access to the system to ensure that the entire private water system, including
the plumbing and all related fixtures are disinfected in accordance with this
rule, prior to placing that private water system into service.
(3)
For initial and
periodic disinfection of cisterns and hauled water storage tanks, all loose
debris, sediment, mineral encrustation and bacterial slime shall be removed
from the cistern or hauled water storage tank prior to disinfection, and either
of the following procedures implemented:
(a)
A solution of
fifty milligrams per liter of chlorine shall be prepared in a storage
container. The quantity of solution prepared shall be of sufficient volume to
disinfect the entire cistern, hauled water storage tank, and all related
storage, or pressure tanks, existing plumbing and attached fixtures;
or
(b)
A solution of two hundred fifty milligrams per liter of
chlorine shall be prepared in a storage container and thoroughly sprayed on all
surfaces of the tank for a period of fifteen minutes. A second solution of
fifty milligrams per liter of chlorine shall then be circulated through the
water supply system and distribution lines.
(O)
All
rainwater cistern and hauled water storage tank that are no longer being used
as a primary water source as a private water system shall be decommissioned in
accordance with rule
3701-28-17 of the Administrative
Code.