Ohio Admin. Code 3717-1-05.1 - Water, plumbing, and waste: plumbing system
An air gap between the water supply inlet and the flood level
rim of the plumbing fixture, equipment, or nonfood equipment
shall
is to be
at least twice the diameter of the water supply inlet and
may not be less than one inch (twenty-five
millimeters).
A backflow or backsiphonage prevention device installed on a
water supply system shall
is to meet American society of sanitary engineering
(ASSE) standards and as referenced in the Ohio plumbing code for construction,
installation, maintenance, inspection, and testing for that specific
application and type of device.
A water filter, screen, and other water conditioning device
installed on water lines shall
is to be designed to facilitate disassembly for
periodic servicing and cleaning. A water filter element
shall
is to be
of the replaceable
type.
At least one handwashing sink, a number of handwashing sinks
necessary for their convenient use by food
employees in areas specified under paragraph (L) of this rule, and not fewer
than the number of handwashing sinks required
mandated by
the Ohio plumbing code shall
is to be provided. This paragraph does not
prohibit
preclude the use of,
when approved by the licensor, of:
automatic handwashing facilities that are capable of
removing the types of soils encountered in the food operation if the food
service operation or retail food establishment has at least one handwashing
sink.
(1) Automatic handwashing facilities
that are capable of removing the types of soils encountered in the food
operation if the food service operation or retail food establishment has at
least one handwashing sink; or
(2) Chemically treated towelettes
for handwashing when food exposure is limited and handwashing sinks are not
conveniently available, such as in some mobile food service operations, mobile
retail food establishments, temporary food service operations, temporary retail
food establishments, or at some vending machine locations.
Toilets and urinals shall
are to be
provided according to the Ohio plumbing code.
At least one service sink or one curbed cleaning facility
equipped with a floor drain shall
is to be provided and conveniently located for the
cleaning of mops or similar wet floor cleaning tools and for the disposal of
mop water and similar liquid waste.
A plumbing system shall
is to be installed to preclude backflow of a solid,
liquid, or gas contaminant into the water supply system at each point of use at
the food service operation or retail food establishment, including on a hose
bibb if a hose is attached or on a hose bibb if a hose is not attached and
backflow prevention is required
mandated by the Ohio plumbing code, by:
A backflow prevention device shall
is to be
provided on a carbonator as required
mandated by the Ohio plumbing code.
A handwashing sink shall
is to be
located:
A backflow prevention device shall
is to be located
so that it may be serviced and maintained.
A water filter, screen, and other water conditioning device
installed on water lines shall
is to be located to facilitate disassembly for
periodic servicing and cleaning.
A device such as a water treatment device or backflow preventer
shall
is to be
scheduled for inspection and service, in accordance with manufacturer's
instructions and as necessary to prevent device failure based on local water
conditions, and records demonstrating inspection and service
shall
are to
be maintained by the person in charge.
A plumbing system shall
is to be:
Notes
Promulgated Under: 119.03
Statutory Authority: 3717.04, 3717.05
Rule Amplifies: 3717.04, 3717.05
Prior Effective Dates: 03/01/2001, 03/01/2005, 03/01/2009, 03/01/2019