Ohio Admin. Code 3745-267-199 - Inspection requirements - tank systems - standardized permitting
Owners or operators shall comply with the following requirements for scheduling, conducting, and documenting inspections.
(A)
Develop and follow a schedule and procedure for
inspecting overfill controls.
(B)
Inspect at least
once each operating day:
(1)
Aboveground portions of the tank system to detect
corrosion or releases of waste.
(2)
Data gathered
from monitoring and leak detection equipment (for example, pressure or
temperature gauges, monitoring wells) to ensure that the tank system is being
operated according to the tank system's design.
(3)
The construction
materials and the area immediately surrounding the externally accessible
portion of the tank system, including the secondary containment system (for
example, dikes) to detect erosion or signs of releases of hazardous waste (for
example, wet spots, dead vegetation).
(C)
Inspect cathodic
protection systems, if present, according to, at a minimum, the following
schedule to ensure that the systems are functioning properly:
(1)
Confirm that the
cathodic protection system is operating properly within six months after
initial installation and annually thereafter.
(2)
Inspect and test
all sources of impressed current, as appropriate, at least every other
month.
(D)
Document, in the operating record of the facility, an
inspection of those items in paragraphs (A) to (C) of this
rule.