Ohio Admin. Code 3745-51-752 - Pumps in light liquid service - equipment leaks
(A)
(1)
Each pump in light liquid service shall be monitored
monthly to detect leaks by the methods specified in paragraph (B) of rule
3745-51-763 of the
Administrative Code except as provided in paragraphs (D), (E), and (F) of this
rule.
(2)
Each pump in light liquid service shall be checked by
visual inspection each calendar week for indications of liquids dripping from
the pump seal.
(B)
(1)
If an instrument
reading of ten thousand parts per million (ppm) or greater is measured, a leak
is detected.
(2)
If there are indications of liquids dripping from the
pump seal, a leak is detected.
(C)
(1)
When a leak is detected, the leak shall be repaired as
soon as practicable, but not later than fifteen calendar days after the leak is
detected, except as provided in rule
3745-51-759 of the
Administrative Code.
(2)
A first attempt at repair (e.g., tightening the packing
gland) shall be made no later than five calendar days after each leak is
detected.
(D)
Each pump equipped with a dual mechanical seal system
that includes a barrier fluid system is exempt from the requirements of
paragraph (A) of this rule, provided the following requirements are met:
(1)
Each dual
mechanical seal system shall be:
(a)
Operated with the barrier fluid at a pressure that is
at all times greater than the pump stuffing box pressure; or
(b)
Equipped with a
barrier fluid degassing reservoir that is connected by a closed-vent system to
a control device that complies with the requirements of rule
3745-51-760 of the
Administrative Code; or
(c)
Equipped with a system that purges the barrier fluid
into a hazardous secondary material stream with no detectable emissions to the
atmosphere.
(2)
The barrier fluid system shall not be a hazardous
secondary material with organic concentrations ten per cent or greater by
weight.
(3)
Each barrier fluid system shall be equipped with a
sensor that will detect failure of the seal system, the barrier fluid system,
or both.
(4)
Each pump shall be checked by visual inspection, each
calendar week, for indications of liquids dripping from the pump
seals.
(5)
(a)
Each sensor as
described in paragraph (D)(3) of this rule shall be checked daily or be
equipped with an audible alarm that shall be checked monthly to ensure that it
the alarm is functioning properly.
(b)
The
remanufacturer or other person who stores or treats the hazardous secondary
material shall determine, based on design considerations and operating
experience, a criterion that indicates failure of the seal system, the barrier
fluid system, or both.
(6)
(a)
If there are indications of liquids dripping from the
pump seal or the sensor indicates failure of the seal system, the barrier fluid
system, or both based on the criterion determined in paragraph (D)(5)(b) of
this rule, a leak is detected.
(b)
When a leak is
detected, it the leak shall be repaired as soon as practicable, but not later
than fifteen calendar days after the leak is detected, except as provided in
rule 3745-51-759 of the
Administrative Code.
(c)
A first attempt at repair (e.g., re-lapping the seal)
shall be made no later than five calendar days after each leak is
detected.
(E)
Any pump that is
designated, as described in paragraph (G)(2) of rule
3745-51-764 of the
Administrative Code, for no detectable emissions, as indicated by an instrument
reading of less than five hundred parts per million (ppm) above background, is
exempt from the requirements of paragraphs (A), (C), and (D) of this rule if
the pump meets the following requirements:
(1)
Has no externally
actuated shaft penetrating the pump housing.
(2)
Operates with no
detectable emissions as indicated by an instrument reading of less than five
hundred ppm above background as measured by the methods specified in paragraph
(C) of rule
3745-51-763 of the
Administrative Code.
(3)
Is tested for compliance with paragraph (E)(2) of this
rule initially upon designation, annually, and at other times as requested by
the director.
(F)
If any pump is equipped with a closed-vent system
capable of capturing and transporting any leakage from the seal to a control
device that complies with the requirements of rule
3745-51-760 of the
Administrative Code, the pump is exempt from the requirements of paragraphs (A)
to (E) of this rule.
Notes
Five Year Review (FYR) Dates: Exempt
Promulgated Under: 119.03
Statutory Authority: 3734.12
Rule Amplifies: 3734.12
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.