[Comment: For dates of non-regulatory government publications,
publications of recognized organizations and associations, federal rules, and
federal statutory provisions referenced in this rule, see the last paragraph of
rule 3745-76-01 of the Administrative
Code titled"Incorporation by reference."] Each owner or operator of an MSW
landfill with a gas collection and control system used to comply with the
provisions of paragraph (B)(2)(b) of rule
3745-76-07 of the Administrative
Code shall:
(A) Operate the collection
system such that gas is collected from each area, cell, or group of cells in
the MSW landfill in which solid waste has been in place for:
(1) Five years or more if active; or
(2) Two years or more if closed or
at final grade.
(B)
Operate the collection system with negative pressure at each wellhead except
under the following conditions:
(1) A fire or
increased well temperature. The owner or operator shall record instances when
positive pressure occurs in efforts to avoid a fire. These records shall be
submitted with the annual reports as provided in paragraph (F)(1) of rule
3745-76-12 of the Administrative
Code;
(2) Use of a geomembrane or
synthetic cover. The owner or operator shall develop acceptable pressure limits
in the design plan;
(3) A
decommissioned well. A well may experience a static positive pressure after
shut down to accommodate for declining flows. All design changes shall be
approved by the director;
(C) Operate each interior wellhead in the
collection system with a landfill gas temperature less than fifty five degrees
Celsius and with either a nitrogen level less than twenty percent or an oxygen
level less than five per cent. The owner or operator may establish a higher
operating temperature, nitrogen, or oxygen value at a particular well. A higher
operating value demonstration shall show supporting data that the elevated
parameter does not cause fires or significantly inhibit anaerobic decomposition
by killing methanogens.
(1) The nitrogen
level shall be determined using Method 3C of Appendix A of 40 CFR Part
60,
unless an alternative test method is established as allowed by paragraph
(B)(2)(a) of rule
3745-76-07 of the Administrative
Code.
(2) Unless an alternative
test method is established as allowed by paragraph (B)(2)(a) of rule
3745-76-07 of the Administrative
Code, the oxygen shall be determined by an oxygen meter using Method 3A of
Appendix A of 40 CFR Part
60 except that:
(a)
The span shall be set so that the regulatory limit is between twenty and fifty
per cent of the span;
(b) A data
recorder is not required;
(c) Only
two calibration gases are required, a zero and span, and ambient air may be
used as the span;
(d) A calibration
error check is not required;
(e)
The allowable sample bias, zero drift, and calibration drift are plus or minus
ten per cent.
(D) Operate the collection system so that the
methane concentration is less than five hundred parts per million above
background at the surface of the landfill. To determine if this level is
exceeded, the owner or operator shall conduct surface testing around the
perimeter of the collection area and along a pattern that traverses the
landfill at thirty meter intervals and where visual observations indicate
elevated concentrations of landfill gas, such as distressed vegetation and
cracks or seeps in the cover. The owner or operator may establish an
alternative traversing pattern that ensures equivalent coverage. A surface
monitoring design plan shall be developed that includes a topographical map
with the monitoring route and the rationale for any site-specific deviations
from the thirty meter intervals. Areas with steep slopes or other dangerous
areas may be excluded from the surface testing.
(E) Operate the system such that all
collected gases are vented to a control system designed and operated in
compliance with paragraph (B)(2)(c) of rule
3745-76-07 of the Administrative
Code. In the event the collection or control system is inoperable, the gas
mover system shall be shut down and all valves in the collection and control
system contributing to venting of the gas to the atmosphere shall be closed
within one hour; and
(F) Operate the
control or treatment system at all times when the collected gas is routed to
the system.
(G) If monitoring
demonstrates that the operational requirements in paragraph (B), (C), or (D) of
this rule are not met, corrective action shall be taken as specified in
paragraphs (A)(3) to (A)(5) of rule
3745-76-10 of the Administrative
Code or paragraph (C) of rule
3745-76-10 of the Administrative
Code. If corrective actions are taken as specified in rule
3745-76-10 of the Administrative
Code, the monitored exceedance is not a violation of the operational
requirements in this rule.
Notes
Ohio Admin. Code
3745-76-08
Five Year Review (FYR) Dates:
03/24/2016 and
03/24/2021
Promulgated
Under: 119.03
Statutory
Authority: 3704.03(E)
Rule Amplifies:
3704.03(A),
3704.03(E)
Prior Effective Dates: 1/31/98, 11/16/99,
10/10/06
R.C. 119.032 review dates:
06/16/2011 and
06/16/2016
Promulgated
Under: 119.03
Statutory Authority: 3704.03(E)
Rule
Amplifies: 3704.03(A), 3704.03(E)
Prior Effective Dates: 1/31/98,
11/16/99, 10/10/06