Chapter 11 of the International
Building Code, 2021 edition, as incorporated by reference and modified in
Section 101.1.1 of this code, is further modified as follows:
(A)
Replace
section 1102.1 with the
following:
1102.1
Design.
Buildings and
facilities are to be designed and constructed to be
accessible
in
accordance with this code and ICC A117.1. Any references to ICC A117.1
throughout this code are to be applied with the following amendment:
1.
Change the last
sentence in Section 603.3 of ICC A117.1, to
read:
Where mirrors are located above
counters that do not contain lavatories, the bottom edge of the reflecting
surface of the mirror is to be 35 inches (890 mm) maximum above the
floor.
(B)
Add new
section 1102.2 to read as
follows:
1102.2
Existing buildings.
Existing buildings are to comply with Chapter 34. Where an
existing building is required to comply with the provisions of Chapter 11, any
reference to ICC A117.1 is to the edition of ICC A117.1 identified in Chapter
35 of this code.
(C)
Modify
section 1104.4 Exception #1 as
follows:
Add the phrase "per
story" after the area limit of 3,000 square feet
(278.7m2) in exception #1.
(D)
Modify
section 1110.1 as follows:
Change the range of sections from
"1110.2 through 1110.16" to "1110.2 through 1110.18."
(E)
Replace the
exceptions to section 1110.2.1.2 to read as follows:
Exception:
The following additional fixtures and equipment are
permitted in a family or assisted-use toilet room.
1.
A
urinal.
2.
A child-height water closet.
3.
A child-height
lavatory.
4.
Adult and baby changing stations.
5.
Other fixtures and
equipment that may be required by other provisions of this
code.
(F)
Add new section
1110.17 as follows:
1110.17
Mail
receptacles.
Where provided, mail
receptacles are to be
accessible
in
accordance with Sections 1110.17.1 or 1110.17.2.
1110.17.1
Dwelling units and sleeping units.
Where mail receptacles are provided for
Accessible
,
Type
A
or
Type B dwelling
and
sleeping
units
,
accessible
mail
receptacles are to be provided in accordance with 1110.17.1.1 or
1110.17.1.2.
1110.17.1.1
Centralized mail receptacles.
Where each individual mail compartment of a centralized
mail receptacle is assigned to a specific
dwelling unit
or
sleeping
unit
, the individual mail compartments
are to comply with 1110.17.1.1.1 or 1110.17.1.1.2.
1110.17.1.1.1
Buildings without an elevator.
In a structure without an elevator, all individual mail
compartments assigned to
Accessible
Units
,
Type A Units
and
Type B
Units
in each location are to be
accessible
.
1110.17.1.1.2
Buildings with an elevator.
In a structure with an elevator, fifty percent of all
individual mail compartments in each location are to be
accessible
.
Individual mail compartments assigned to
Accessible
and
Type A units
are to be included in the
accessible
mailboxes.
1110.17.1.1.3
Parcel lockers.
All
parcel lockers of centralized mail receptacles are to be
accessible
.
1110.17.1.2
Individual house-mounted and curbside mail
receptacles.
Where an individual
house-mounted or curbside mail receptacle serves a
dwelling unit
or
sleeping
unit
that is required to be an
Accessible unit
,
Type A
unit
or
Type B unit
, the mail
receptacle are to be
accessible
.
1110.17.2
Other
occupancies
. Where mail receptacles are
provided in occupancies not falling within the purview of Section 1110.17.1, at
least 5 percent, but not less than one, of each type in each location, are to
be
accessible
.
(G)
Add new
section 1110.18 as follows:
1110.18
Adult
changing stations.
Where provided, adult
changing stations are to include a changing table that meets the requirements
of 1110.18.5 and are to be
accessible
in
accordance with ICC A117.1 and Section 1113. Where adult changing stations are
required per Section 1110.18.1, compliance with Sections 1110.18.2 through
1110.18.5 is also required.
1110.18.1
Where required.
At least one adult changing station is to be provided
in all the following locations:
1.
In assembly and mercantile occupancies, where family or
assisted-use toilet or bathing rooms are required by Section 1110.2.1.
Exception:
Where the use is as a nightclub, bar, tavern, dance
hall or similar purpose, the adult changing station is to be provided where a
family or assisted-use toilet or bathing room is required by Section 1110.2.1
and the occupant load is 450 or greater.
2.
In Group B
occupancies providing educational facilities for students above the 12th grade,
where an aggregate of twelve of more male and female water closets are required
to serve the classrooms and lecture halls.
3.
In Group E
occupancies, where a room or space used for assembly purposes requires an
aggregate of six or more male and female water closets for that room or
space.
4.
In highway rest stops and highway service
plazas.
1110.18.2
Room.
Adult
changing stations are to be located in toilet rooms that include only one water
closet and only one lavatory. Fixtures located in such rooms are to be included
in determining the number of fixtures provided in an occupancy. The occupants
are to have access to the required adult changing station at all times that the
associated occupancy is occupied.
Exception:
Adult changing stations are permitted to be located in
family or assisted-use toilet rooms required in Section 1110.2.1.
1110.18.3
Prohibited location.
The accessible route to an accessible adult changing station
is prohibited to include travel through security checkpoints.
1110.18.4
Travel distance.
The
adult changing stations station is to be located on an
accessible route
such
that a person is no more than two stories above or below the story with the
adult changing station and the path of travel to such facility is less than
2000 feet.
1110.18.5
Adult changing table safety
features.
Adult changing tables are to
include the following safety features:
1.
A retractable
safety rail in accordance with Section 1113.4.4,
2.
A changing surface
that is durable, non-absorbent and resistant to corrosion, and
3.
Designed to
support a weight of not less than 400 lbs. (182 kg) applied to any point on the
changing surface.
(H)
Replace
section 1111.1 with the
following:
1111.1
Scope.
Recreational
facilities located within a building that is within the scope of this code are
to comply with this section. Provisions of the federal law, contained in
Chapters 2 and 10 of the 2010 ADA Standards for Accessible Design, may apply to
the design of recreational facilities that are outside the scope of this
code.
(I)
Add a note and exceptions at the end of section
1111.4.8.2 to read as follows:
Note:
Coordination is to be performed for amusement rides
regulated by the Ohio department of agriculture to determine whether the ride
provides at least one wheelchair space, amusement ride seat designed for
transfer, or transfer device.
Exceptions:
1.
Amusement rides
that are controlled or operated by the rider are not required to comply with
this section.
2.
Amusement rides designed primarily for children, where
children are assisted on and off the ride by an adult, are not required to
comply with this section.
3.
Amusement rides that do not provide seats that are
built-in or mechanically fastened are not required to comply with this
section.
(J)
Replace section 1111.4.8.3 with the
following:
1111.4.8.3
Minimum number.
Deleted.
(K)
Add new
section 1111.4.16 to read as follows:
1111.4.16
Golf
Facilities.
Buildings and amenities
serving a golf course, such as parking areas, golf cart rental stations, toilet
rooms, clubhouses and other structures are to be
accessible
and be located on an
accessible route.
1111.4.16.1
Golf Courses.
Golf
course elements directly associated with practicing and playing the golf course
such as the tee grounds, tee boxes, putting greens, golf cart paths, practice
putting greens, practice teeing grounds, and teeing stations at driving ranges
are not regulated by this code.
(L)
Add new
section 1112.1.1 to read as follows:
1112.1.1
Signs
to designate accessible parking spaces and passenger loading
zones.
Accessible
parking spaces, van-
accessible
spaces and
passenger loading zones required by section 1106 to be reserved for individuals
with disabilities, are to be provided with a sign mounted on a fixed or movable
post or otherwise affixed in a vertical position so that the sign is clearly
visible to the driver of a vehicle when parked in such a location. A notice is
to be affixed to this sign or posted adjacent to it that states the amount of
the fine established by section
4511.99 of the Revised Code for
the offense of parking a vehicle in this location if it is not legally entitled
to do so.
Note
: The fine
established by section
4511.99 of the Revised Code is
to be not less than two hundred fifty dollars nor more than five hundred
dollars.
(M)
Add new
section 1113 to read as follows:
SECTION
1113
ADULT CHANGING STATION
ACCESSIBILITY
1113.1
General.
Adult changing stations are to be on an
accessible route
and
are to comply with Section
1113.2 through
1113.4. See Section
1110.18 for additional
requirements applicable to required adult changing stations.
1113.2
Installation location.
Required adult changing stations are to be installed in
accordance with Section 1113.2.1. Non-required adult changing stations are to
be installed in accordance with Section 1113.2.1, 1113.2.2 or 1113.2.3 based on
the proposed location of the adult changing station.
1113.2.1.
Single user or family or assisted-use toilet or bathing
room.
Where adult changing stations are
provided in a toilet room with only one water closet and one lavatory, or in a
family or assisted-use toilet or bathing room, the room is to have all of the
following components:
1.
A dispenser for soap complying with Section 308 of ICC
A117.1.
2.
A hand towel dispenser or hand dryer complying with
Table 603.6 of ICC A117.1.
3.
A coat hook located in close proximity to the changing
surface.
4.
A waste receptacle.
5.
Signage indicating
"Adult Changing Station" provided at the entrance to the room and complying
with the visual character requirements in Section
703.2 of ICC
A117.1.
6.
Signage indicating the weight capacity and instructions
for operation of the changing station within the room.
1113.2.2
Multi-user toilet or bathing room.
Where adult changing stations are provided in a
multi-user toilet or bathing room, the adult changing station is to be located
in a compartment that includes all of the following components:
1.
Privacy provided
by walls, curtains or partitions enclosing the compartment.
2.
A turning space
complying with Section 304 of ICC A117.1.
3.
A lavatory
complying with Section 606 of ICC A117.1.
4.
A dispenser for
soap complying with Section 308 of ICC A117.1.
5.
A hand towel
dispenser or hand dryer complying with Table 603.6 of ICC
A117.1.
6.
A coat hook in close proximity to the changing
surface.
7.
A waste receptacle.
8.
Signage indicating
"Adult Changing Station" provided at the entrance to the room and complying
with the visual character requirements in Section
703.2 of ICC
A117.1.
9.
Signage indicating the weight capacity and instructions
for operation of the changing station within the compartment.
1113.2.3
Room or space other than a toilet room or bathing
room.
Where adult changing stations are
provided in a room or space other than a toilet or bathing room and including,
but not limited to, nurses' work areas, therapist work areas, or special
education classrooms, the adult changing station is to be located in a
compartment or room that includes all of the following components:
1.
Privacy provided
by walls, curtains or partitions.
2.
A turning space
complying with Section 304 of ICC A117.1.
3.
A lavatory
complying with Section 606 of ICC A117.1 or an alcohol-based hand sanitizer
dispenser.
4.
Where a lavatory is provided in the compartment or
room, provide a dispenser for soap.
5.
Where a lavatory
is provided in the compartment or room, provide a hand towel dispenser or hand
dryer complying with Table 603.6 of ICC A117.1.
6.
A waste
receptacle.
7.
Signage indicating the weight capacity and instructions
for operation of the changing station within the room.
1113.2.4
Directional signage to adult changing stations.
The locations of the adult changing stations are to be
identified on any directional graphic of the facility used to orient the public
visitor.
1113.3
Room clearances.
An adult changing station and its supporting structure
is not permitted to obstruct the required clear floor spaces and clearances at
accessible elements, maneuvering clearances at doors, or the wheelchair turning
spaces.
1113.4
Changing surface.
A
changing surface is to be provided and is to comply with Section
1113.4.
1113.4.1
Size.
The changing
surface is to be 70 inches (1778mm) minimum in length and 30 inches (762mm)
minimum in width.
1113.4.2
Height adjustability.
The changing surface height is to be adjustable at
variable heights from 17 inches (432mm) minimum to 38 inches (965mm) maximum
above the floor as measured to the top of the changing surface.
Exception:
Where the adult changing station is not required, a
fixed height changing surface is permitted and is to be mounted with the top of
the changing surface 19 inches (483mm) minimum and 23 inches (584 mm) maximum
above the floor.
1113.4.3
Clearances.
Clearances
complying with Sections 1113.4.3.1 and 1113.4.3.2 are to be provided adjacent
to the changing surface, measured when the surface is in the operational
position.
1113.4.3.1
Side clearance.
A side
clearance measuring 36-inch (914mm) wide, minimum, is to be provided along the
entire length of at least one long side of the changing surface.
Exception:
In the raised position, the side rail is permitted to
overlap the side clearance.
1113.4.3.2
End
clearance.
An end clearance measuring
36-inch (914mm) wide, minimum, is to be provided along the entire length of at
least one short side of the changing surface. The end clearance is to extend
the depth of the changing surface and the side clearance.
Exceptions:
1.
A 24-inch (610 mm)
wide minimum end clearance is permitted where a clear floor space complying
with Section 305.3 of ICC A117.1 is provided
within the room beyond the clearances for the changing surface.
2.
Where installed
in locations specified in Section 1113.2.3, end clearances complying with
Section 1113.4.3.2 is not required.
1113.4.4
Side
rail.
Side rails are to comply with
Sections 1113.4.4.1 and 1113.4.4.2.
1113.4.4.1
Size
and location.
Side rails are to be a
minimum of 2/3 of the length of the changing surface and are to be centered +/-
3 inch (75 mm) along the long open sides of the changing
surface.
1113.4.4.2
Rail positioning.
Side rails are to be capable of being raised and
lowered. The side rail is to be fixed in place when in the raised position. The
top of the side rail is to extend 5 inches (127mm) minimum above the top of the
changing surface.
Replaces: 4101:1-11-01
Notes
Ohio Admin. Code 4101:1-11-01
Effective:
3/1/2024
Five Year Review (FYR) Dates:
03/01/2029
Promulgated
Under: 119.03
Statutory Authority: 3781.10(A)(1), 3781.111
Rule Amplifies: 3781.10, 3781.11, 3781.111, 3791.04