Chapter 10 of the International
Plumbing Building Code, 2021 edition, as incorporated by reference and modified
in Section 101.1.1 of this code, is further modified as follows:
(A)
Replace
section 1001.1 with the
following:
1001.1
Scope.
This chapter
governs the material and installation of traps, interceptors and separators
when installed inside a building and not on the building sewer. The rules of
the "Ohio Environmental Protection Agency" may also govern the design and
installation of pretreatment devices such as traps, interceptors, and
separators.
(B)
Replace the first paragraph of section
1002.1 with the following, but
retain the four exceptions intact:
1002.1
Fixture
traps.
Each plumbing fixture is to be
separately trapped by a liquid-seal trap, except as otherwise permitted by this
code. A fixture is not to be double trapped.
(C)
Add new
section 1002.1.1 to read as follows:
1002.1.1
Vertical distance.
The
vertical distance from the fixture outlet to the trap weir is not to exceed 24
inches (610 mm).
Exception:
The height of a clothes washer standpipe above a trap
is to conform to Section 802.4.3.
(D)
Add new
section 1002.1.2 to read as follows:
1002.1.2
Horizontal distance.
The horizontal distance is not to exceed 30 inches (610 mm)
measured from the centerline of the fixture outlet to the centerline of the
inlet of the trap.
(E)
Modify
section 1002.4.1 to add an exception as follows:
Exception:
Trap seal protection is not required in garage floor
drains in one-, two-, and three-family dwellings.
(F)
Modify
section 1003.1 as follows:
Replace the word "Interceptors" with
the phrase "Where required by the local sewer purveyor or as otherwise required
in this section, interceptors"
(G)
Add new
section 1003.1.1 to read as follows:
1003.1.1
Industrial processes, meat packing and food processing
facilities.
Wastes from industrial
processes, meat packing and food processing facilities and similar processing
plants are to be drained in accordance with the rules of the "Ohio
Environmental Protection Agency", or the authority in charge of the sewage
system into which the wastes are to be discharged. (See sections
6111.44 and
6111.45 of the Revised
Code.)
(H)
Modify section
1003.4 as follows:
Add the word "and" after "facilities,",
delete the phrase "and hydraulic elevator pits" and delete the exception as
shown below.
Exception:
Deleted.
Replaces: 4101:3-10-01
Notes
Ohio Admin. Code 4101:3-10-01
Effective:
3/1/2024
Five Year Review (FYR) Dates:
03/01/2029
Promulgated
Under: 119.03
Statutory Authority: 3781.10(A)(1)
Rule
Amplifies: 3781.03(D), 3781.10, 3781.11, 3791.04
Prior Effective
Dates: 03/01/1998, 04/01/1999, 01/01/2002, 07/01/2007, 11/01/2011, 07/01/2014,
11/01/2017