(A) All existing
boilers and pressure vessels and the associated equipment, controls, devices,
and safeguards
shall
are to be maintained in a safe and sanitary condition,
in good working order, and free of leaks and defects. The owner or the owner's
designated agent
shall be
is responsible for the maintenance of such boilers and
pressure vessels and associated equipment, controls, devices, and safeguards.
If the original stamping, marking, or
nameplate becomes illegible, detached, or lost, the owner or user is to have
the stamped data, markings, or nameplate replaced in accordance with the
applicable part of the "NBIC" as referenced in rule
4101:4-3-01 of the
Administrative Code.
(B) The rules of the board
shall
are not
to be retroactively applied to existing boilers
or pressure vessels that are not otherwise being altered, repaired,
reinstalled, or relocated. Portions of a boiler or pressure vessel not altered
or repaired and not affected by an alteration or repair are not required to
comply with the code requirements for a new boiler or pressure
vessel.
(C) Routine boiler repairs
such as piping or tube replacement or repairs considered general maintenance
may be made without permit or inspection. However, routine repairs that involve
welding do require a permit and approval
must
is to be
obtained from a general or special inspector prior to performing the repair. In
the case where the contractor or owner making the routine repair has obtained a
"National Board "R" Certificate of Authorization", the authorized inspector
shall
is to
authorize the routine repair prior to the work being performed. If the repair
requires welding,
it shall
the welding is to be
performed in accordance with the provisions of section
IX of the "ASME Boiler and Pressure Vessel Code" as referenced in rule
4101:4-3-01 of the
Administrative Code.
(D) Where a
major repair or alteration (including a re-rating) is necessary or desired on
an existing boiler which bears the stamp of the appropriate "ASME" symbol or
which is stamped with a state of Ohio boiler number, the repair or alteration
shall
is to
comply with the requirements of "Part 3" of the "NBIC" as referenced in rule
4101:4-3-01 of the
Administrative Code. The repair or alteration
shall
is to meet the
requirements for the conditions under which it will be operated.
(1) In accordance with rule
4101:4-7-01 of the
Administrative Code, unless the contractor or owner has obtained a "National
Board "R" Certificate of Authorization", all contractors or owners
shall
are to
apply for a permit from the division of industrial compliance to make proposed
repairs and the repairs
shall
are to be approved by a special or general inspector.
A repair report, executed and signed by the special or general inspector,
shall
is to be
filed with the superintendent on forms provided.
(2) In accordance with
"Part 3" of the "NBIC," contractors or owners
performing boiler alterations shall
are to obtain a "National Board "R" Certificate of
Authorization" prior to making any alterations. All alterations
shall
are to
be authorized and approved by an authorized inspector.
(E) Where a major repair or alteration
(including a re-rating) is necessary or desired on an existing boiler or
pressure vessel which does not bear the appropriate "ASME" symbol stamp or
which is not stamped with a state of Ohio boiler number, the boiler or pressure
vessel
shall
is
to be evaluated by the superintendent and required to meet the applicable
requirements of the "ASME Boiler and Pressure Vessel Code" referenced in rule
4101:4-3-01 of the
Administrative Code. Otherwise, the boiler or pressure vessel
shall
is to be
retired from use.
(F) Repairs made
to an existing "Ohio Special" boiler or pressure vessel
shall
are to
be done in accordance with paragraph (C), (D)(1), or (H)(1) of this rule, as
applicable.
(G) Alterations,
including re-ratings, made to an existing "Ohio Special" boiler or pressure
vessel
shall
are
to be approved, prior to the alteration, by the board of building
standards in accordance with the special procedure outlined in rule
4101:4-5-01 of the
Administrative Code for boilers and pressure vessels of special
design.
(H) Where a major repair or
alteration (including a re-rating) is necessary or desired on an existing
pressure vessel which bears the stamp of the appropriate "ASME" symbol, the
repair or alteration
shall
is to comply with the requirements of "Part 3" of the
"NBIC" as referenced in rule
4101:4-3-01 of the
Administrative Code. The repair or alteration
shall
is to meet the
requirements for the conditions under which it will be operated.
(1) Unless the contractor or owner has
obtained a "National Board "R" Certificate of Authorization", all contractors
or owners shall
are
to notify the division of industrial compliance prior to making repairs
to an existing pressure vessel and the repairs shall
are to be
approved by a special or general inspector. A repair report, executed and
signed by the special or general inspector, shall
is to be filed
with the superintendent on forms provided.
(2) In accordance with
"Part 3" of the "NBIC", contractors or owners
performing pressure vessel alterations shall
are to obtain a
"National Board "R" Certificate of Authorization" prior to making any
alterations. All alterations shall
are to be authorized and approved by an authorized
inspector.
(I) Whenever
repairs are made to fittings, safety devices, appliances, or controls or it
becomes necessary or desirable to replace them, the work
shall
is to
comply with the requirements for new installations as prescribed in the
applicable section of the
"ASME Boiler and Pressure Vessel Code" and the applicable part of the "NBIC" as referenced in
rule 4101:4-3-01 of the
Administrative Code. When an owner wishes to install safety devices and
controls which will enable an existing boiler to be operated without
continuous, manned attendance by a licensed operator, the requirements of
paragraph (B)(4) or (B)(5) of rule
4101:4-10-01 of the
Administrative Code shall
are to be met.
(J) An existing stationary boiler or pressure
vessel which bears the appropriate "ASME" symbol or which is stamped with a
state of Ohio boiler number may be reinstalled or relocated within Ohio,
provided that the installation complies with the applicable section of the
"ASME Boiler and Pressure Vessel Code" as referenced in rule
4101:4-3-01 of the
Administrative Code and an inspection is made by a special or general inspector
prior to operation. The fittings and appliances
shall
are to comply
with the requirements for a new installation.
(K) A secondhand boiler or pressure vessel
stamped with the appropriate "ASME" symbol or having the standard stamping of
another state that has adopted rules of construction equivalent to those of
Ohio may be installed for use in the state of Ohio provided that application is
made for the installation, the manufacturer's data report, indicating that the
boiler or pressure vessel was inspected during construction by an authorized
inspector, is filed in the office of the superintendent, and an inspection is
made by a special or general inspector prior to operation. The inspector
shall
is to
submit a report to the superintendent which contains a facsimile of the code
stamping, a statement concerning any corrosion or other deteriorating
conditions and the extent and location of any welded or riveted repairs. Upon
approval of a secondhand boiler by the superintendent, a certificate of
operation shall
is
to be issued.
(L) Except as
permitted in paragraph (K) of this rule, an existing boiler or pressure vessel
that does not bear the appropriate "ASME" symbol, was not registered with the
"National Board," does not have a state of Ohio boiler number stamped upon it,
or does not have an "Ohio Special" serial number tagged upon it is prohibited
from reinstallation or relocation within the state of Ohio.
(M) The maximum allowable steam working
pressure for cast iron boilers, except for hot water boilers,
shall
is to
be fifteen psig.
(N) The maximum
allowable working pressure on the shell or drum of an existing nonstandard
boiler
shall
is
to be determined by the strength of the weakest section of the structure,
computed from the thickness of the plate, the tensile strength of the plate,
the efficiency of the longitudinal joint or the tube ligaments, the inside
diameter of the weakest course and the factor of safety allowed by these rules.
(S)(t)(E)/(R)(F) = Maximum allowable working pressure,
psig.
Where:
S = ultimate tensile strength of shell plates, psi.
When the ultimate tensile strength, "S", of steel or
wrought-iron shell plates is not known, it shall
is to be taken
as fifty-five thousand psi for steel and forty-five thousand psi for
wrought-iron.
t = minimum thickness of shell plate, in weakest course,
inch.
E = efficiency of longitudinal joint.
For riveted construction, "E" shall
is to be
determined by rules given in paragraph "PR-15" of the 1971 edition of the "ASME
Boiler and Pressure Vessel Code, section I."
For tube ligaments, "E" shall
is to be
determined by rules "PG-52" or, "PG-53" of the "ASME Boiler and Pressure Vessel
Code, section I" and "PR-25", of the 1971 edition of the "ASME Boiler and
Pressure Vessel Code, section I."
R = inside radius of the weakest course of the shell or drum in
inches.
F = factor of safety permitted.
(1) When computing the ultimate strength of
rivets in shear, the following values in pounds per square inch of the
cross-sectional area of the rivet shank (after driving)
shall
is to
be used:
Strength of existing rivets in shear
|
Type of rivet
|
Strength
|
|
Iron rivet in single shear
|
38,000
|
|
Iron rivet in double shear
|
76,000
|
|
Steel rivets in single shear
|
44,000
|
|
Steel rivets in double shear
|
88,000
|
(2)
When the diameter of the rivet holes in the longitudinal joints of a boiler is
not known, the diameter and cross sectional area of rivets, after driving, may
be ascertained from the following table or by cutting out one rivet in the body
of the joint:
Sizes of rivets in inches based on plate thickness
|
Thickness of plate, inches.
|
1/4
|
9/32
|
5/16
|
11/32
|
3/8
|
13/32
|
|
Diameter of rivet after driving,
inches.
|
11/16
|
11/16
|
3/4
|
3/4
|
13/16
|
13/16
|
|
Thickness of plate, inches.
|
7/16
|
15/32
|
1/2
|
9/16
|
5/8
|
-
|
|
Diameter of rivet after driving,
inches.
|
15/16
|
15/16
|
15/16
|
17/16
|
17/16
|
-
|
(3)
The resistance of steel to crushing shall
is to be taken as ninety-five thousand
psi.
(4) The lowest factor of
safety permissible on existing installations shall
is to be 4.5
excepting for horizontal return tubular boilers having continuous longitudinal
lap seams more than twelve feet in length where the factor of safety
shall
is to be
8, and when this latter type of boiler is removed from its existing setting, it
shall
is not
to be reinstalled for pressure in excess of
fifteen psig. Reinstalled or secondhand nonstandard boilers
shall
are to
have a minimum factor of safety of 6 when the longitudinal seams are of lap
riveted construction, and a minimum factor of 5 when the longitudinal seams are
of butt and double strap construction. A boiler constructed of wrought iron
shall
is to
have a factor of safety of 7. Upon inspection of the boiler, if conditions are
found which justify a reduction of the safe working pressure, the factor of
safety as stated above shall
is to be appropriately increased.
(O) The maximum allowable working pressure of
a nonstandard low pressure steam boiler shall
is not
to exceed fifteen psig.
(P) The maximum allowable working pressure of
a nonstandard boiler constructed principally of cast iron or constructed of a
cast iron shell or heads and steel tubes shall
is not
to exceed thirty psig for hot water
service.
(Q) The maximum allowable
working pressure of a nonstandard water tube boiler, the tubes of which are
secured to cast iron or malleable iron headers, or which have cast iron mud
drums, shall
is not to exceed one
hundred sixty psig for steam service.
(R) If in the judgment of the inspector a low
pressure boiler is unsafe for operation at the pressure previously approved,
the pressure shall
is to be reduced, proper repair made, or the boiler
retired from service.
(S)
Nonstandard pressure vessels except those exempt in section
4104.04 of the Revised Code and
paragraph "U-1" of the "ASME Boiler and Pressure Vessel Code, section VIII",
are prohibited for use in excess of fifteen psi internal or external
pressure.
(T) Any owner or operator
who in any manner loads the safety valve or valves to a greater pressure than
that allowed by the certificate of operation shall
be
is subject to the penalty provided in
section 4104.99 of the Revised
Code.