2301.2
Design
and installation.
The design and
installation of solar thermal energy systems shall comply with Sections
2301.2.1 through 2301.2.13.
2301.2.1
Access.
Access shall be provided to solar energy equipment for
maintenance. Solar systems and appurtenances shall not obstruct or interfere
with the operation of any doors, windows or other building components requiring
operation or access. Roof-mounted solar thermal equipment shall not obstruct or
interfere with the operation of roof-mounted equipment, appliances, chimneys,
plumbing vents, roof hatches, smoke vents, skylights and other roof
penetrations and openings.
2301.2.2
Collectors and panels.
Solar collectors and panels shall comply with Sections
2301.2.2.1 and 2301.2.2.2.
2301.2.2.1
Roof-mounted collectors.
The roof shall be constructed to support the loads
imposed by roof- mounted solar collectors. Roof-mounted solar collectors that
serve as a roof covering shall conform to the requirements for roof coverings
in Chapter 9 of this code. Where mounted on or above the roof coverings, the
collectors and supporting structure shall be constructed of noncombustible
materials or fire-retardant- treated wood equivalent to that required for the
roof construction.
2301.2.2.2
Collector sensors.
Collector sensor installation, sensor location and the
protection of exposed sensor wires from degradation shall be in accordance with
ICC/900/SRCC 300.
2301.2.3
Pressure and temperature relief valves and system
components.
System components containing
fluids shall be protected with temperature and pressure relief valves or
pressure relief valves. Relief devices shall be installed in sections of the
system so that a section cannot be valved off or isolated from a relief device.
Direct systems and the potable water portion of indirect systems shall be
equipped with a relief valve in accordance with the plumbing code as
modified by Chapter 25. For indirect systems, pressure relief valves
in solar loops shall comply with ICC 900/SRCC 300. System components shall have
a working pressure rating of not less than the setting of the pressure relief
device.
2301.2.4
Vacuum relief.
System
components that might be subjected to a vacuum during operation or shutdown
shall be designed to withstand such a vacuum or shall be protected with vacuum
relief valves.
2301.2.5
Piping insulation.
Piping shall be insulated in accordance with the
requirements of Chapter 11. Exterior insulation shall be protected from
ultraviolet degradation. The entire solar loop shall be insulated. Where
split-style insulation is used, the seam shall be sealed. Fittings shall be
fully insulated.
Exceptions:
1.
Those portions of
the piping that are used to help prevent the system from overheating shall not
be required to be insulated.
2.
Those portions of
piping that are exposed to solar radiation, made of the same material as the
solar collector absorber plate and are covered in the same manner as the solar
collector absorber, or that are used to collect additional solar energy, shall
not be required to be insulated.
3.
Piping in thermal
solar systems using unglazed solar collectors to heat a swimming pool shall not
be required to be insulated.
2301.2.6
Protection from freezing.
System components shall be protected from damage
resulting from freezing of heat-transfer liquids at the winter design
temperature provided in Table 301.2(1). Freeze protection shall be provided in
accordance with ICC 900/SRCC 300. Drain-back systems shall be installed in
compliance with Section 2301.2.6.1. Systems utilizing freeze-protection valves
shall comply with Section 2301.2.6.2.
Exception:
Where the 97.5 -percent winter design temperature is
greater than or equal to 48°F (9°C).
2301.2.6.1
Drain-back systems.
Drain-back systems shall be designed and installed to allow
for manual gravity draining of fluids from areas subject to freezing to
locations not subject to freezing, and air filling of the components and
piping. Such piping and components shall maintain a horizontal slope in the
direction of flow of not less than one-fourth unit vertical in 12 units
horizontal (2-percent slope). Piping and components subject to manual gravity
draining shall permit subsequent air filling upon drainage and air venting upon
refilling.
2301.2.6.2
Freeze-protection valves.
Freeze-protection valves shall discharge in a manner
that does not create a hazard or structural damage.
2301.2.7
Storage tank sensors.
Storage tank sensors shall comply with ICC 900/SRCC
300.
2301.2.8
Expansion tanks.
Expansion tanks in solar energy systems shall be installed
in accordance with Section 2003 in solar collector loops that contain
pressurized heat transfer fluid. Where expansion tanks are used, the system
shall be designed in accordance with ICC 900/SRCC 300 to provide an expansion
tank that is sized to withstand the maximum operating pressure of the
system.
Exception:
Expansion tanks shall not be required in the collector
loop of drain-back systems.
2301.2.9
Roof
and wall penetrations.
Roof and wall
penetrations shall be flashed and sealed in accordance with Chapter 9 to
prevent entry of water, rodents and insects.
2301.2.10
Description and warning labels.
Solar thermal systems shall comply with description
label and warning label requirements of Section 2301.2.11.2 and ICC 900/SRCC
300.
2301.2.11
Solar loop.
Solar loops
shall be in accordance with Sections 2301.2.11.1 and 2301.2.11.2.
2301.2.11.1
Solar loop isolation.
Valves shall be installed to allow the solar loop to be
isolated from the remainder of the system.
2301.2.11.2
Drain and fill valve labels and caps.
Drain and fill valves shall be labeled with a
description and warning that identifies the fluid in the solar loop and a
warning that the fluid might be discharged at high temperature and pressure.
Drain caps shall be installed at drain and fill valves.
2301.2.12
Maximum temperature limitation.
Systems shall be equipped with means to limit the
maximum water temperature of the system fluid entering or exchanging heat with
any pressurized vessel inside the dwelling to 180°F (82°C). This
protection is in addition to the required temperature and pressure relief
valves required by Section 2301.2.3.
2301.2.13
Deleted.
2301.3
Labeling.
Labeling
shall comply with Sections 2301.3.1 and 2301.3.2.
2301.3.1
Collectors and panels.
Solar thermal collectors and panels shall be listed and
labeled in accordance with ICC 901/SRCC 100. Factory-built collectors shall
bear a label indicating the manufacturer's name, model number and serial
number.
2301.3.2
Thermal storage units.
Pressurized water storage tanks shall bear a label
indicating the manufacturer's name and address, model number, serial number,
storage unit maximum and minimum allowable operating temperatures and storage
unit maximum and minimum allowable operating pressures. The label shall clarify
that these specifications apply only to the water storage
tanks.
2301.7
Solar
thermal systems for heating potable water.
Where a solar thermal system heats potable water to supply a
potable hot water distribution system, the solar thermal system shall be in
accordance with Sections 2301.7.1, 2301.7.2 and the plumbing code as
modified by Chapter 25.
2301.7.1
Indirect systems.
Heat
exchangers that are components of indirect solar thermal heating systems shall
comply with Section the plumbing code as modified by Chapter
25.
2301.7.2
Direct systems.
Where potable water is directly heated by a solar
thermal system, the pipe, fit-tings, valves and other components that are in
contact with the potable water in the solar heating system shall comply with
the requirements of the plumbing code as modified by Chapter
25.